Chapter 3
Setup and Power-On Procedures
33
2. Connect the Sun Fire V445 server’s outlet plug of each power cord to the power
sequencer in the cabinet (if your type of cabinet includes one), to a grounded
outlet strip, or to a grounded AC power outlet.
Caution –
High leakage current. To prevent leakage current in excess of 3.5 mA, a
maximum of two power cords can be connected to a single branch circuit. The
remaining two power cords must be connected to a different branch circuit.
Note –
Each inlet must connect the server to a 15A circuit for North America and
Japan, and to a 10A or 16A circuit for Europe. Consult your local electrical codes for
any additional requirements. See the instructions provided with your cabinet for
information about the power sequencer.
Note –
At this point, all system information is delivered to you by way of the
ALOM system controller and its software. ALOM is the default method for
communicating with the Sun Fire V445 server. For detailed information about using
ALOM, consult the
Sun Advanced Lights Out Manager
(
ALOM) 1.6 Online Help
and
the
Sun Fire V445 Server Administration Guide
, which includes information about
reconfiguration options.
3. Continue setup with the section,
“Preparing to Configure the Primary Network
.