51
10 CASCADING
10.1 Appliance
The S-CBX boilers have an internal flue gas valve for an
overpressure system according to below table. This device is
needed to prevent recirculation of the flue gases.
TABLE
Maximum vertical length in metres.
Type of
boiler
Number of
appliances
DN150
DN150/200
DN200
DN200/300
S-CBX 85
2
30
30
30
30
3
30
30
30
30
4
-
30
30
30
5
-
-
30
30
6
-
-
-
30
S-CBX
105
2
30
30
30
30
3
30
30
30
30
4
-
-
30
30
5
-
-
-
30
6
-
-
-
30
S-CBX
125
2
30
30
30
30
3
-
30
30
30
4
-
-
15
30
5
-
-
-
30
6
-
-
-
30
S-CBX
155
2
27
30
30
30
3
-
30
30
30
4
-
-
-
30
5
-
-
-
30
6
-
-
-
30
Remark 1: DN 150/200 means: the diameter of the horizontal collector including the bend = 150 mm and after
the bend the diameter of the vertical section is 200 mm with an adaptor of 150->200 mm
Remark 2: Horizontal length between shaft and last collector = 1 m. Greater length decreases the maximum
vertical length of the table.
Remark 3: For calculating other lengths between the last collector and the bend, the length of the vertical
height must be reduced by the number of length and for bends the following table must be used.
Diameter
Elbow type
150
200
45°
1.7
m. equiv. length
3.8
m. equiv. length
90°
4.0
m. equiv. length
5.8
m. equiv. length
Содержание S-CBX 105
Страница 2: ......
Страница 40: ...40 9 10 Flue Terminal Positioning ...
Страница 42: ...42 9 11 1 FIGURE 12 LINE G ...
Страница 55: ...55 11 5 Ladder Logic Diagram ...
Страница 56: ...56 11 6 Electrical schematics ...
Страница 57: ...57 ...
Страница 137: ......