46
9.13.2 E
XAMPLE
B:
T
WIN PIPE SYSTEM WITH CONCENTRIC ROOF TERMINAL
Calculation example with given lengths: checking resistance
Boiler type:
S-CBX 125
Flue gas
Diameter: 100 mm
Number
Pa
Pa total
Straight tube /m
total
6
5.0
30.0
Bend
90°
2
18.3
36.6
Roof terminal
concentric
100/150
1
55.7
55.7
Adaptor conc./par. 100-100 >
100/150
1
0.8
0.8
Total resistance flue gas outlet:
123.1
A
ir
su
pp
ly
Diameter: 100 mm
Number
Pa
Pa total
Straight tube /m
total
6
5.8
34.8
Bend
90°
2
21.2
42.4
Roof terminal
concentric
100/150
1
74.2
74.2
Adaptor conc./par. 100-100 >
100/150
1
70.0
70.0
Total resistance air supply:
221.4
Total resistance flue gas outlet and air supply:
344.5
The total resistance is more than 200 Pa.
This flue gas / air supply system is NOT functional.