background image

 

86 

14.3  Lockout codes 

 

 

 

Lock

out 

code

 

Error

 

Description

 

Cause

 

Solving

 

E2PROM_READ

_ERROR 

Internal software error 

wrongly 

programmed PCB 

or PB 

reset PCB or replace PCB 

and or display unit 

IGNIT_ERROR 

Five unsuccessful ignition 

attempts in a row 

no gas, wrongly 

adjusted gas valve  

check gas supply and 

adjust gas valve, reset 

PCB 

GV_RELAY_ 

ERROR 

Failure detected in the gas 

valve relay 

short circuit in coil 

of the gas valve, 

water on wiring or 

gas valve  

reset PCB replace gas valve 

or wiring harness 

SAFETY_RELAY

_ERROR 

Failure detected in safety 

relay 

safety relay is not 

working correctly 

reset PCB or replace PCB 

BLOCKING_ 

TOO_LONG 

Control had a blocking error 

for more than 20 hours 

blocking code 

active for more than 

20 hours 

reset and check blocking 

code 

FAN_ERROR_ 

NOT_RUNNING 

Fan is not running for more 

than 60 seconds 

electrical wiring not 

correctly 

connected, or Fan 

is malfunctioning 

Check wiring or replace Fan 

if not solved check fuse on 

PCB or replace PCB 

FAN_ERROR_ 

TOO_SLOW 

Fan runs too slow for more 

than 60 seconds 

electrical wiring not 

correctly 

connected, or Fan 

is malfunctioning 

Check wiring or replace Fan 

if not solved check fuse on 

PCB or replace PCB 

FAN_ERROR_ 

TOO_FAST 

Fan runs too fast for more 

than 60 seconds 

electrical wiring not 

correctly 

connected, or Fan 

is malfunctioning 

Check wiring or replace Fan 

if not solved check fuse on 

PCB or replace PCB 

RAM_ERROR 

Internal software error 

wrongly 

programmed PCB 

or PB 

reset PCB or replace PCB 

and or display unit 

WRONG_EEPR

OM_SIGNATUR

Contents of E2prom is not 

up to date 

out dated E2prom  

reset PCB or replace PCB 

10 

E2PROM_ 

ERROR 

Wrong safety parameters in 

E2prom 

wrongly 

programmed PCB 

or PB 

reset PCB or replace PCB 

11 

STATE_ERROR  Internal software error 

wrongly 

programmed PCB 

or PB 

reset PCB or replace PCB 

12 

ROM_ERROR 

Internal software error 

wrongly 

programmed PCB 

or PB 

reset PCB or replace PCB 

13 

APS_NOT_ 

OPEN 

Air pressure switch not 

opening during pre-purge 0 

electrical circuit is 

short circuited or 

APS is jammed 

check wiring or replace APS  

14 

APS_NOT_CLO

SED_IN_PRE_ 

PURGE 

Air pressure switch not 

closing during pre-purge 1 

no air transport to 

the burner; flue or 

air inlet is blocked 

or APS is jammed 

or air signal hose 

not connected to 

the air intake pipe 

or water in hose  

 

Check if there are any 

obstructions in the flue or air 

intake, replace APS if 

jammed, connect air hose to 

the air intake pipe, remove 

any water from the hose. 

Содержание S-CBX 105

Страница 1: ...s 85 105 125 155 Wall Hung High Efficiency Condensing Boiler Installation Operating Maintenance Manual Please read and understand before commencing installation and leave the manual with the customer for future reference 2019 02 01 v2 ...

Страница 2: ......

Страница 3: ...LITY 20 7 9 FROST PROTECTION 20 7 10 INSTALLING A STRAINER AND OR DIRT SEPARATOR 21 7 11 WATER QUALITY 21 7 12 USE OF GLYCOL 22 7 13 CHEMICAL WATER TREATMENT 22 7 14 FLUSH THE SYSTEM WITH FRESH WATER 23 7 15 PLASTIC PIPING IN THE HEATING SYSTEM 23 7 16 DE AIR SEQUENCE 24 7 17 AUTOMATIC FEED VALVE SYSTEMS 24 7 18 WATER PRESSURE 25 7 19 INSTALLATION EXAMPLES 25 7 19 1 Example of a normal single boil...

Страница 4: ... AND DISPLAY 60 12 1 DISPLAY AND BUTTONS 60 12 1 1 Display icons 61 12 2 SCREENS AND SETTINGS 61 12 2 1 Set Actual setpoint DHW setpoint directly via the Status overview 61 12 2 2 Entering the menu 62 12 2 3 Protected menu items 63 12 2 4 De aeration Sequence 63 12 2 5 Language settings 63 12 3 BOILER HISTORY 64 12 4 ERROR LOGGING 64 12 5 GENERAL 65 12 5 1 Pump start exercise every 24 hours 65 12 ...

Страница 5: ...7 3 THIRD CHECK THE WATER FLOW 103 17 4 MOUNTING CONDENSATE TRAP 104 17 5 CHECKING GAS PRESSURE 104 17 6 FIRING FOR THE FIRST TIME 104 18 ADJUSTING AND SETTING THE BOILER 105 18 1 INTRODUCTION 105 18 1 1 Combustion table 105 18 1 2 Setting screws venturi and gas valves drawings 106 18 2 ADJUSTMENT PROCEDURES 107 18 3 VENTURI REPLACEMENT ADJUSTMENT 107 18 4 CONVERSION FROM NATURAL GAS TO PROPANE 10...

Страница 6: ...3 22 12 10 General Settings 133 22 12 11 Language 133 22 12 12 Unit Type 133 22 12 13 Date Time 133 22 12 14 Time zone settings 133 22 12 15 Display settings 133 22 12 16 Cascade mode 133 22 12 17 Other Settings 134 22 12 18 Boiler settings 134 22 13 BOILER HISTORY 134 22 14 ERROR LOGGING 134 22 15 SERVICE REMINDER 135 22 15 1 Service overdue logging 135 22 15 2 Service reminder implementations 13...

Страница 7: ...pliance and to replace any part of the control system and any gas control which has been under water What to do if you smell gas Do not use any electrical equipment Do not press any switches Close the gas supply Ventilate the room open the windows and or outdoor water heater room doors Immediately warn the installer The manufacturer supplier is not liable for any damage caused by inaccurately foll...

Страница 8: ...n from each boiler Weather compensation control Calorifier control Connections for On Off thermostat 0 10 VDC remote flow temperature set point control 0 10 VDC remote burner input control Outdoor temperature sensor External calorifier pump or diverter valve Boiler pump PWM control for external boiler pump System pump External flow switch or external safety device Modbus External system sensor DHW...

Страница 9: ...54 4 Nominal input net G31 kW 16 0 80 5 19 0 95 2 24 1 120 8 39 3 142 2 Nominal output 80 60 C G20 kW 14 9 79 1 18 0 94 2 22 9 115 7 33 9 140 9 Nominal output 50 30 C G20 kW 16 0 85 1 19 5 101 8 24 7 124 7 36 4 151 0 Nominal output 37 30 C G20 kW 16 6 88 4 20 2 105 5 25 6 129 4 38 0 157 8 Nominal output 80 60 C G25 3 kW 15 2 77 0 18 1 92 3 23 1 113 4 34 3 137 9 Nominal output 50 30 C G25 3 kW 16 4...

Страница 10: ... 20 C C 60 90 Mass flow flue gas min max g s 8 0 42 10 51 12 62 15 76 Available pressure for the flue system 4 Pa 200 INSTALLATION Resistance boiler T 20 K m W C 4 0 3 4 3 8 3 6 T 25 K m W C 2 8 2 3 2 5 2 4 Pressure boiler min max bar 1 0 6 0 Max flow temperature C 90 ELECTRIC Maximum power consumption 5 W 190 280 280 280 Power supply V Hz 230 50 Protection class IPX4D NOTES 3 CO2 of the unit meas...

Страница 11: ...8 8 46 5 Seasonal space heating energy efficiency ɳs 92 4 92 6 92 7 92 9 Energy efficiency ɳ4 at 60 80 C 87 2 87 2 87 3 87 3 Energy efficiency ɳ1 at 30 37 C 97 4 97 6 97 7 97 8 Auxiliary electricity consumption At full load elmax kW 0 183 0 271 0 280 0 278 At part load elmin kW 0 024 0 023 0 027 0 031 In standby mode Psb kW 0 007 0 007 0 007 0 007 Other Standby heat loss Pstby kW 0 066 0 070 0 075...

Страница 12: ...S CONNECTIONS 4 1 S CBX 85 105 Twin Pipe Concentric Coaxial Connections Twin Pipe Concentric A Flow BSP 1 B Return BSP 1 C Condensate Flexible hose Ø 25 21 mm D Gas BSP Flue gas 100 mm 100 150 mm Air inlet 100 mm 100 150 mm ...

Страница 13: ... D 4 2 S CBX 125 Twin Pipe Concentric Coaxial Connections Twin Pipe Concentric A Flow BSP 1 B Return BSP 1 C Condensate Flexible hose Ø 25 21 mm D Gas BSP Flue gas 100 mm 100 150 mm Air inlet 100 mm 100 150 mm ...

Страница 14: ...14 A B C D 4 3 S CBX 155 Twin Pipe Only Connections Twin Pipe A Flow BSP 1 B Return BSP 1 C Condensate Flexible hose Ø 25 21 mm D Gas BSP 1 Flue gas 150 mm Air inlet 150 mm ...

Страница 15: ...culating Pump for S CBX 155 S022 500 013 WIFI module IP module S022 500 006 External ignition transformer S022 500 016 Propane orifice S CBX 85 105 S022 500 001 Propane orifice S CBX 125 S022 500 004 Propane orifice S CBX 155 S022 500 010 5 2 Unpacking The S CBX boiler will be supplied with the following documents and accessories One Installation user and service instructions manual for the instal...

Страница 16: ... related to the boiler location The ventilation of the boiler room must meet local and national standards and regulations regardless of the selected supply of fresh air to the boiler The flue gas pipes must be connected to the outside wall and or the outside roof The installation area must be dry and frost free The boiler has a built in fan that will generate noise depending on the total heat dema...

Страница 17: ...included suspension bracket or a suspension frame when supplied While marking the holes ensure that the suspension bracket or frame is perpendicular and the boiler does not lean forward If necessary adjust the position with the adjusting bolts at the lower rear side of the back panel see drawing When the adjusting bolts aren t sufficient fill the gap behind the bolts to get the boiler in position ...

Страница 18: ...ondensate drain Metal lines are not allowed Blockage of this drain might damage the boiler The drain connection is correct when the condensate can be seen flowing away e g using a funnel Any damage that might occur when the drain is not installed correctly is not covered by the warranty of the boiler There should be an open connection of the condensate hose into the sewage system A possible vacuum...

Страница 19: ...sel in the return pipe of the central heating system It can be combined with the drain valve for service See the drawing 7 5 Pressure relief valve The boiler has no internal pressure relief valve This should be installed close to the boiler in the flow pipe of the heating system When having cascaded boilers each boiler should have its own pressure relief valve It is recommended to install service ...

Страница 20: ...onitoring A high temperature difference between supply and return of the boiler can indicate a clogged heat exchanger or filter or a defective pump The burner load automatically decreases when the Return Supply temperature differential increases too much See chapter 13 Temperature protection 7 9 Frost protection The boiler has a built in frost protection that is automatically activating the centra...

Страница 21: ...y to seep in are suction gaskets pumps air valve working as a venting pipe O rings gaskets in stuffing box under floor heating pipes When a boiler is installed in a new system or an existing installation the system must be cleaned before the boiler is installed The system is required to be cleaned using a system cleaner from the list below or an equivalent hydronic system cleaner Follow the instru...

Страница 22: ...fic anti freeze products has been tested by the heat exchanger producer These products mainly consist of glycol next to the described additives If these products are used according to the instruction they will not harm the boiler These anti freeze products are Manufacturer Type Composition Fernox Alphi 11 consists of 97 Mono Propylene Glycol next to some additives Sentinel X500 estimated as being ...

Страница 23: ...ircuit should be free of any particles debris and pollution Therefore the complete installation must always be thoroughly flushed with clean water before installing and using the boiler s 7 15 Plastic piping in the heating system When plastic pipes with no oxygen barrier e g under floor heating system are used in the central heating system these should be separated from the boiler system by using ...

Страница 24: ...essure is stable again In that case the De Air sequence will last longer than the estimated minutes The following scheme below shows the behaviour of the 3 way valve and general pump during one whole cycle of De Air sequence with a DAir_Repeation_OnOff set to 2 Relevant variables Specific Parameters Level Default Value Range De Air Config Configuration for the De Air function 2 Installer 1 0 24 hr...

Страница 25: ... between 1 5 and 2 0 bar The pressure sensor will stop the boiler from firing when the water pressure drops below 0 7 bar and start the boiler firing again when the water pressure reaches above 1 0 bar Higher pressure systems e g in high buildings If pressures higher than 6 0 bar occurs in the heating system the best solution is to separate the system from the boiler by means of a plate heat excha...

Страница 26: ...26 7 19 2 EXAMPLE OF A MULTIPLE BOILER HEATING CIRCUIT WITH LOW LOSS HEADER HEATING ZONE BOILER BOILER NON RETURN VALVE low resistance type NOT SPRING LOADED ...

Страница 27: ...h 0 0 2 0 4 0 6 0 8 0 10 0 0 0 1 0 2 0 3 0 4 0 5 0 HEAD mwc FLOW m3 h S CBX 85 HYDRAULIC GRAPH BOILER PUMP INSTALLATION ΔT 20K ΔT 25K 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 0 10 0 0 0 1 0 2 0 3 0 4 0 5 0 HEAD mwc FLOW m3 h S CBX 105 HYDRAULIC GRAPH BOILER PUMP INSTALLATION ΔT 20K ΔT 25K ...

Страница 28: ...y the Default Duty cycle parameter How the pump is modulated is controlled with the Modulating_Pump_Mode setting 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 0 10 0 3 0 3 5 4 0 4 5 5 0 5 5 6 0 6 5 7 0 HEAD mwc FLOW m3 h S CBX 125 HYDRAULIC GRAPH BOILER PUMP INSTALLATION ΔT 20K ΔT 25K 0 0 2 0 4 0 6 0 8 0 10 0 4 0 4 5 5 0 5 5 6 0 6 5 7 0 7 5 8 0 HEAD mwc FLOW m3 h S CBX 155 HYDRAULIC GRAPH BOILER PUMP INST...

Страница 29: ...a The pump speed increases so there is less time to cool down the heated water This results in the T_Return temperature increasing Actual delta temperature is smaller than the selected T_Delta The pump speed decreases so there is more time to cool down the heated water This results in the T_Return temperature decreasing 8 4 Pump maximum electrical power General The inrush current of a conventional...

Страница 30: ...ot installed accordingly it may result in condensate building up in the flue gas tube eventually causing component failure Wall flue terminals are generally used up to 80 kW Using these terminals with larger capacities will give unpleasant large condensate clouds When using a wall terminal there is the possible risk of ice building up on surrounding parts structures because the condensate will fre...

Страница 31: ... and engineering See also the cascade chapter for these multiple boiler installations READ THE MANUAL PROVIDED BY THE VENT GAS AND AIR SYSTEM SUPPLIER CAREFULLY 9 2 Polypropylene This product has been approved for use with polypropylene vent with the manufacturers listed All terminations must comply with listed options in this manual and be a single wall vent offering For support and special conne...

Страница 32: ...flue products to the outside while using combustion air from the equipment room In order to use the room air venting option the following conditions and considerations must be followed The equipment room MUST be provided with properly sized openings to assure adequate combustion air There will be a noticeable increase in the noise level during normal operation from the inlet air opening Vent syste...

Страница 33: ...nd in household laundry rooms Adhesives used to fasten building products and other similar products Areas likely to have contaminants Dry cleaning laundry areas and establishments Swimming pools Metal fabrication plants Beauty shops Refrigeration repair shops Photo processing plants Auto body shops Plastic manufacturing plants Furniture refinishing areas and establishments New building constructio...

Страница 34: ...See Typical examples example C Be aware The installation room has to have sufficient air supply vents These vents must be open and may not be closed or blocked Requirements at NEN 3028 paragraph 6 5 C13 Closed Air supply from outside Wall outlet Air supply inlet and flue gas outlet at the same air pressure zone a combined wall outlet e g See Typical examples example E Air inlet Flue outlet Vented ...

Страница 35: ...stem for the supply of combustion air and discharge of combustion products Condensate is allowed to go to the boiler Air supply inlet and flue gas outlet not at opposite walls Technical data nominal Tflue gas 85 C nominal Qfluegas see 3 2 11 maximum Tfluegas 90 C min load Tfluegas 35 C min load Qfluegas see 3 2 11 nominal CO2 see 3 2 11 max allowed draft 70 Pa max pressure drop inlet outlet 200 Pa...

Страница 36: ...scharges the products of combustion to the outside through orifices that are either concentric or close enough to come under similar wind conditions The C 10 appliance is designed to become connected to a common duct system that is designed to operate under the conditions where the static pressure in the common flue duct might exceed the static pressure in the common air duct A type C x 3 applianc...

Страница 37: ...to a common duct system which is designed for more than one appliance The appliance is connected via a second of its ducts to a terminal which supplies air to the appliance from outside the building The C 13 appliance is designed to become connected to its common duct where the static pressure might exceed the static pressure in its individual air supply duct A type C x 3 appliance incorporating a...

Страница 38: ...m of the combustion chamber heat exchanger 9 8 C63 certified If a heater is C63 certified the flue gas and air supply parts should have a separate CE marking according the building products regulations The parts must be able to handle the condensate forming W and transport overpressure P1 and must have a minimum temperature class of T120 Also it has to meet the requirements in the chapters 6 4 and...

Страница 39: ... 750mm is more than the minimum 600mm the required height will be 750mm Example 2 If the maximum snow level on the roof surface is 150mm then the air inlet would be at 150 300 450mm This 450 mm is less than the minimum 600 mm so the height should be 600 mm Height difference B This is the distance between the flue outlet and the air inlet The flue gas outlet should be at least 700 mm above the air ...

Страница 40: ...40 9 10 Flue Terminal Positioning ...

Страница 41: ...the horizontal flue run is suitable or not If the flue run is unsuitable then it is recommended to change the terminal position to either a horizontal position which answers no to all the below questions or design the flue run to discharge vertically Risk Assessment is as per IGEM UP 10 Edition 4 ...

Страница 42: ...42 9 11 1 FIGURE 12 LINE G ...

Страница 43: ...10 1 14 9 150 straight tube m 0 4 0 5 0 8 1 1 45 bend 0 6 0 8 1 3 1 9 90 bend 1 4 2 0 3 0 4 4 Flue outlet zeta 0 05 0 1 0 1 0 2 0 3 Flue outlet zeta 1 0 1 8 2 5 3 8 5 6 Flue outlet zeta 1 5 2 7 3 8 5 7 8 4 Roof terminal 3 0 4 3 6 5 9 6 reducer 150 to 130 1 9 2 6 4 0 5 9 AIR SUPPLY 100 straight tube m 2 7 3 8 5 8 45 bend 6 2 8 7 13 1 90 bend 9 9 14 1 21 2 air inlet zeta 1 0 10 4 14 8 22 3 130 strai...

Страница 44: ...e m 7 4 10 5 15 8 45 bend 6 5 9 2 13 8 90 bend 9 4 13 4 20 1 roof terminal 34 7 49 3 74 2 wall terminal 34 7 49 3 74 2 adaptor 32 8 46 5 70 0 Never reduce pipe diameters relative to boiler connections Values printed in grey applicable for larger pipe diameters than boiler connection NOTICE This table may only be used for a single flue air system for one boiler Do NOT use this table for common flue...

Страница 45: ...YSTEM WITH SEPARATE PIPES FOR FLUE OUTLET AND AIR SUPPLY Calculation example with given lengths checking resistance Boiler type S CBX 155 Flue gas Diameter 150 mm quantity Pa Pa total Straight tube m total 9 1 1 9 9 Bend 90 2 4 4 8 8 Flue outlet zeta 1 0 1 5 6 5 6 Total resistance flue gas outlet 24 3 Air supply Diameter 150 mm quantity Pa Pa total Straight tube m total 8 1 3 10 4 Bend 90 2 5 1 10...

Страница 46: ... 100 150 1 55 7 55 7 Adaptor conc par 100 100 100 150 1 0 8 0 8 Total resistance flue gas outlet 123 1 Air supply Diameter 100 mm Number Pa Pa total Straight tube m total 6 5 8 34 8 Bend 90 2 21 2 42 4 Roof terminal concentric 100 150 1 74 2 74 2 Adaptor conc par 100 100 100 150 1 70 0 70 0 Total resistance air supply 221 4 Total resistance flue gas outlet and air supply 344 5 The total resistance...

Страница 47: ...l pipe length includes 4 bends 90 adaptor par conc conc roof terminal 8 3 Example A C63 Boiler Type S CBX 85 S CBX 105 S CBX 125 S CBX 155 Diameter air pipe mm 100 100 100 150 Diameter flue pipe mm 100 100 100 150 Diam roof terminals mm 100 100 100 150 Maximum pipe length m flue air total pipe length includes 4 bends 90 flue outlet zeta 1 0 air inlet zeta 1 0 40 8 21 2 5 9 108 1 Concentric roof te...

Страница 48: ...2 Bend 45 2 7 5 15 0 Flue outlet zeta 1 0 1 12 8 12 8 Total resistance flue gas 94 9 The total resistance is less than 200 Pa This flue gas air supply system is functional Example C B23 B23P Boiler Type S CBX 85 S CBX 105 S CBX 125 S CBX 155 Diameter air pipe mm 100 100 100 150 Diameter flue pipe mm 100 100 100 150 Diam roof terminal mm 100 100 100 150 Maximum pipe length m includes 2 bends 90 2 b...

Страница 49: ...flue gas and air supply 245 9 The total resistance is more than 200 Pa This flue gas air supply system is NOT functional 9 13 5 EXAMPLE E CONCENTRIC SYSTEM WALL OUTLET C13 WALL MOUNTED Calculation example with given lengths checking resistance Boiler type S CBX 85 FLUE GAS Diameter 100 150 mm quantity Pa Pa total Straight tube m total 9 2 4 21 6 Bend 90 1 8 5 8 5 Concentric terminal wall 1 9 0 9 0...

Страница 50: ...oncentric roof terminal mm 100 150 100 150 100 150 Maximum pipe length m includes 2 bends 90 2 bends 45 roof terminal 12 4 Example E C13 Boiler Type S CBX 85 S CBX 105 S CBX 125 S CBX 155 Diameter concentric pipe mm 100 150 100 150 100 150 NOT POSSIBLE Concentric wall terminal mm 100 150 100 150 100 150 Maximum pipe length m includes 1 bend 90 wall terminal 36 8 18 4 3 5 ...

Страница 51: ...S CBX 155 2 27 30 30 30 3 30 30 30 4 30 5 30 6 30 Remark 1 DN 150 200 means the diameter of the horizontal collector including the bend 150 mm and after the bend the diameter of the vertical section is 200 mm with an adaptor of 150 200 mm Remark 2 Horizontal length between shaft and last collector 1 m Greater length decreases the maximum vertical length of the table Remark 3 For calculating other ...

Страница 52: ... cable glands NOTICE Before starting to work on the boiler it must be switched off and the power supply to the boiler must be disconnected Electrical wiring should be installed according to all applicable standards and regulations Working on the boiler should only be done by a qualified service engineer that is skilled in working on electrical installations and according to all applicable standard...

Страница 53: ... HEATING CIRCUIT OPTION 1 An ON OFF thermostat can be connected If these terminals are bridged the set programmed flow temperature of the boiler will be used OPTION 2 An OpenTherm OT controller can be connected to these terminals The boiler software will detect and use this OpenTherm signal automatically PARAMETER Boiler parameter 124 see chapter 11 9 programmable in and outputs 14 15 0 10 VDC CON...

Страница 54: ...hapter 11 9 programmable in and outputs 6 PE 7 BOILER PUMP Connections for the power supply of a boiler pump P1 see chapter 8 4 for detailed electrical specifications 8 9 PE PE MAINS SUPPLY The power supply connection of the unit 8 Line voltage wire 9 Neutral wire PE Ground wire 10 11 ALARM RELAY A semiconductor alarm output This is a triac output with an active voltage of 230 VAC it can only hand...

Страница 55: ...55 11 5 Ladder Logic Diagram ...

Страница 56: ...56 11 6 Electrical schematics ...

Страница 57: ...57 ...

Страница 58: ...T_Return O O O O M O O M T_DHW M M M M M M T_Outdoor O O O O O O O 0 10 Volt O O O O O O O O O Water Flow DHW O O O O O M O M M RT Switch O O M O O O O O O M Mandatory O Optional Disabled N A Not Available DHW mode 0 No Domestic Hot Water DHW mode 1 Storage with sensor DHW mode 2 Storage with thermostat DHW mode 3 Instantaneous water heating with plated heat exchanger flow switch and DHW out senso...

Страница 59: ...0 Disabled 1 DHW flow sensor 1 Module pump 2 DHW flow switch 2 CH pump 3 CH flow sensor 3 DHW pump 4 CH flow switch 4 System pump 118 Prog Input 3 0 Disabled 5 Cascade pump 1 Drain switch 6 Alarm relay 2 Gas pressure switch 7 Filing valve 122 Prog Input 7 0 Disabled 8 LPG tank 1 T_Flue_2 sensor 9 Ext Igniter 2 T_Flue_2 with blocked flue 10 Air damper 3 Cascade sensor 128 Prog Output 4 0 Disabled 4...

Страница 60: ...m selection in Status overview when directly setting Actual setpoint or DHW setpoint Left Return to previous menu item or Status overview Up Directly select Actual setpoint of DHW setpoint in the Status overview push RIGHT to confirm and use UP or DOWN to adjust value Down Directly select Actual setpoint of DHW setpoint in the Status overview push RIGHT to confirm and use UP or DOWN to adjust valu...

Страница 61: ...ctly via the Status overview When DHW is active you also cannot set the Actual setpoint CH setpoint directly via the Status overview Press UP DOWN to select the mode then press CONFIRM or RIGHT to confirm the mode and the Actual DHW setpoint becomes directly settable Use UP or DOWN to increase decrease the setpoint Press CONFIRM or RIGHT to confirm your alteration or press ESC or LEFT to cancel A ...

Страница 62: ... LEFT If CH mode is set to CH mode 1 CH with an outdoor temperature reset and thermostat control Or CH mode 2 Central Heating with full outdoor temperature reset The following display will appear Enter a menu item by pressing CONFIRM or RIGHT The header shows your location inside the menu as seen in the following image It now is possible to set the Outdoor reset curve by changing the parameters on...

Страница 63: ...ettings Boiler 12 2 4 DE AERATION SEQUENCE The De Aeration sequence is a safety function that starts at every power ON and after reset of the boiler and is used to remove the air from the heat exchanger The display will show the following string during DAir sequence Dair Running Dair Error Water Pressure The DAir sequence can be cancelled by the user by pressing the Enter button for over 5 seconds...

Страница 64: ... the error codes it receives from the boiler s and if an error code is a new error code the error will be stored in the error log An error will be logged with a real time clock time stamp date and time when the error was detected and a boiler ID of the boiler on which the error was detected The error log can be viewed from the error log menu which is located in the information menu Menu Domestic H...

Страница 65: ...e time 2 60 seconds not safety critical Pre ignition time 2 seconds not safety critical Flame failure response time 1 0 second Flame current Minimum 1 0 μA Start detection 1 5 μA Cable length AL BUS1 mm2 AWG Cable length m ft 0 25 23 100 328 1 ft 0 5 20 200 656 2 ft 0 75 18 300 984 3 ft 1 0 17 400 1312 3 ft 1 5 15 600 1968 5 ft 1 This is the total length of the cable not the length between two boi...

Страница 66: ...G Appliance type 52 S CBX 155 on Natural Gas Appliance type 53 S CBX 155 on LPG Appliance type 54 Not Used Appliance type 55 Not Used 12 6 Ignition cycle During the ignition cycle multiple safety checks are active False flame detection If flame is detected at the end of the pre spark period Pre ignite a lockout error occurs Re ignition If at the end of the safety period no flame is detected the co...

Страница 67: ...AME RECOVERY When the ionization current is too low the system responds by increasing the minimal fan speed in order to keep the flame present This is done by increasing the minimal fan speed when the ionization current is too low Whenever the ionization current is high enough the minimal fan speed will be decreased again When the flame still disappears the minimal fan speed will be increased for ...

Страница 68: ...F because the supply temperature reaches CH_Setpoint CH_Hysterese_Up the control will wait a period of time Anti_Cycle_Period 180 sec settable before it is allowed to be switched ON again This function is to prevent short cycling ON and OFF of the boiler However when during the anti cycle wait time the differential between setpoint and supply temperature gets greater than Anti_Cycle_T_Diff anti cy...

Страница 69: ...all for heat is blocked and the pumps are stopped There is a fixed hysteresis of 1 C 1 8 F around the Warm_Weather_Shutdown setting This means that the demand is stopped when the outdoor temperature has risen above Warm_Weather_Shutdown 1 C 1 8 F When the outdoor temperature drops below Warm_Weather_Shutdown 1 C 1 8 F again the demand will also start again Boost function The outdoor reset boost fu...

Страница 70: ...ather Sets low boiler CH setpoint when outdoor temp is equal to Reset_Curve_Outdoor_Mild_Weather 2 Installer 40 ºC 104 ºF 0 40 ºC 32 104 ºF Reset_Curve_Outdoor_Mild_Weather Sets the outdoor temp at which the boiler setpoint must be low as set by Reset_Curve_Mild_Weather 2 Installer 20 ºC 68 ºF 0 30 ºC 32 86 ºF Reset_Curve_Boiler_Minimum Sets the lower limit for the CH setpoint minimum 2 Installer ...

Страница 71: ... using the installer password and changing parameter 28 in the boiler parameters default value is setpoint 4 C Boiler Parameters 25 Warm Weather Shutdn 22 C 26 Boost Temp increment 0 C 27 Boost Time Delay 20 min 28 Night Setback Temp 4 C Adjustable constant Circulation Parameters Parameters Level Default Value Settable CH_Mode 2 Installer 0 Mode 0 5 Warm_Weather_Shutdown Set max outdoor temp Above...

Страница 72: ...adverse condition and override control of the analogue signal to prevent an upset condition This means for example that when signal is going up faster than the boiler can regulate that the boiler will slow down to prevent overshoot in temperature The CH_Setpoint_Min and CH_Setpoint_Max parameters can be adjusted to provide the desired temperature adjustment band A heat request will be generated by...

Страница 73: ...espond to the minimum modulation rate and the maximum modulation analogue input signal value will correspond to the maximum modulation rate All other safety and control functions associated with the boiler will react normally to adverse condition and override control of the analogue signal to prevent an upset condition A heat request will be generated by an input of 1 5 volts or higher The fan spe...

Страница 74: ...ver CH demand but the priority period is limited up to DHW_Max_Priority_Time The priority timer starts when both CH and DHW demand are present After the DHW_Max_Priority_Time is achieved the control will switch from DHW to CH operation CH has priority now for a maximum period of DHW_Max_Priority_Time Different DHW Priority types can be chosen DHW priority Description 0 Time DHW has priority to CH ...

Страница 75: ...ºF 40 85 ºC 104 185 ºF DHW_Priority 2 0 Time 1 OFF 2 ON DHW_Max_Priority_Time Sets the maximum time for either DHW or CH priority 2 Installer 60 min DHW_Post_Pump_Period 2 Installer 120 sec 10 900 12 8 4 INSTANTANEOUS WATER HEATING WITH PLATED HEAT EXCHANGER DHW MODE 3 In DHW mode 3 the water flow through a plated heat exchanger is checked with a flow switch If the switch closes a water flow is de...

Страница 76: ...rted as well The boiler is PID controlled towards the Boiler_Setpoint When the supply temperature rises above boiler setpoint DHW_Supp_Hysterese_Up the boiler is switched OFF When the Anti_Legionella_Sensor is above Anti_Legionella_Setpoint 3 C 37 F for Anti_Legionella_Burn_Time the controller goes into post circulation and ends the Anti Legionella demand When the controller has powered up the Ant...

Страница 77: ...C Installer Set outdoor temperature above which CH demand is locked Bas Outd T 0 30 20 C Installer Set the outdoor temperature at which CH setpoint is set to Bas Supply T Des Outd T 25 25 5 C Installer Set the outdoor temperature at which CH setpoint is set to Des Supply T 2 Domestic Hot Water DHW min max Default unit Access level Description DHW Setpoint 40 71 60 C Installer Set the DHW setpoint ...

Страница 78: ...essful Ignitions User Display the number of successful ignitions Failed Ignitions User Display the number of failed ignitions Flame Failures User Display the number of flame losses Operation Days days User Display the total time in operation CH Burner Hours hrs User Display the amount of burn hours for CH DHW Burner Hours hrs User Display the amount of burn hours for DHW 3 4 Error Log min max Defa...

Страница 79: ...e zone correction Daylight Savings Time User Select the daylight savings time mode B Display settings min max Default unit Access level Description Time Notation 24h 24h 12h User Select 24h or 12h time notation Date Order User Select the date format Day of Month 2 1 or 2 dig User Select how the day of month is displayed Month User Select how the month is displayed Year 4 2 or 4 dig User Select how...

Страница 80: ...i cycling period 9 Anti Cycle Temp Diff 0 20 16 C Installer Set the burner anti cycling differentia 10 Design Supply Temp 4 90 85 C Installer Set CH setpoint when outdoor temperature equals Des Outd T 19 Design Outdoor Temp 25 25 5 C Installer Set the outdoor temperature at which CH setpoint is set to Des Supply T 20 Baseline Supply Temp 4 90 40 C Installer Set CH setpoint when outdoor temperature...

Страница 81: ... for the programmable RT input 124 Prog Output 1 0 10 4 Installer Select the function for programmable output 1 125 Prog Output 2 0 10 9 Installer Select the function for programmable output 2 126 Prog Output 3 0 10 6 Installer Select the function for programmable output 3 127 Prog Output 4 0 20 18 Installer Select the function for programmable output 4 128 Mod Pump dT 5 40 20 C Installer Set the ...

Страница 82: ...a module is started 144 Hyst Up Quick Stop 0 40 6 C Installer Set the fast hysteresis up after which a module is stopped 145 Hyst Up Stop All 0 60 8 C Installer Set the hysteresis up at which all modules are stopped 146 Number of Units 0 16 1 Installer Set the no of modules expected in the cascade system 147 Power Mode 0 3 2 Installer Set the power mode 148 Max Setp Offset Down 0 20 0 C Installer ...

Страница 83: ... the fast hysteresis down after which a boiler is started 164 Hyst Up Quick Stop 0 40 4 C Installer Set the fast hysteresis up after which a boiler is stopped 165 Hyst Up Stop All 0 60 8 C Installer Set the hysteresis up at which all boilers are stopped 166 Number of boilers 0 16 1 Installer Set the number of boilers expected in the cascade system 167 Power Mode 0 3 2 Installer Set the power mode ...

Страница 84: ...F and 43 C 77 F boiler input modulates between minimum and maximum At min boiler input ΔT above 43 C 77 F is allowed Hx_Diff_DeltaT_Min 8 C 14 4 F Above ΔT 48 C 86 F the boiler is switched OFF during HX_Diff_Max_Wait_Time Relevant factory set variables Parameter Level Factory Setting Range HX Diff DeltaT Min 3 Factory 35 ºC 63 ºF 10 80 ºC 18 144 ºF HX Diff Max Wait Time Wait time after upper limit...

Страница 85: ...res Operation days CH Burner Hours DHW Burner Hours 14 2 Boiler history and time stamps Boiler History Via the boiler history screen in the LabVision PC software the following history data is shown Successful ignitions Failed Ignitions Flame Failures Anti Legionella count Total system run time hr Total CH burn time min Total DHW burn time min Error History The last 15 lockout and 15 blocking error...

Страница 86: ...ring or replace Fan if not solved check fuse on PCB or replace PCB 7 FAN_ERROR_ TOO_FAST Fan runs too fast for more than 60 seconds electrical wiring not correctly connected or Fan is malfunctioning Check wiring or replace Fan if not solved check fuse on PCB or replace PCB 8 RAM_ERROR Internal software error wrongly programmed PCB or PB reset PCB or replace PCB and or display unit 9 WRONG_EEPR OM_...

Страница 87: ...10 seconds after closing the gas valve wrong earthing of PCB and boiler Check earthing of PCB and boiler 21 FLAME_BEFOR E_IGNIT Flame is detected before ignition wrong earthing of PCB and boiler Check earthing of PCB and boiler 22 TOO_MANY_ FLAME_LOSS Three time flame lost during 1 demand bad gas supply or CO2 level is not correct or bad ignition rod check gas supply pressure check CO2 level and a...

Страница 88: ... if not so fill up the system 35 APS_NOT_CLO SED_IN_POST_ PURGE Air pressure switch not closing during post purge 1 no air transport to the burner after heat demand flue or air inlet is blocked or APS is jammed or air signal hose not connected to the air intake pipe or water in hose Check if there are any obstructions in the flue or air intake replace APS if jammed connect air hose to the air inta...

Страница 89: ...it Check if the system resistance exceeds the spare capacity of the unit pump 106 REFHI_TOO_HI GH Internal hardware error wrongly programmed PCB or PB reset PCB or replace PCB and or display unit 107 REFHI_TOO_LO W Internal hardware error wrongly programmed PCB or PB reset PCB or replace PCB and or display unit 108 REFLO_TOO_HI GH Internal hardware error wrongly programmed PCB or PB reset PCB or r...

Страница 90: ...onnection to PCB or check resistance NTC sensor 127 SUPPLY_SHOR TED Supply sensor shorted malfunctioning supply sensor or short circuiting check connection to PCB or check resistance NTC sensor 129 DHW_SHORTE D DHW sensor shorted malfunctioning DHW sensor or short circuiting check connection to PCB or check resistance NTC sensor 130 FLUE_SHORTE D Flue sensor shorted malfunctioning Flue sensor or s...

Страница 91: ...pply voltage too high for more than 60 seconds peak in power supply to boiler check power supply 14 5 Warnings Error no Error Description Cause Solving 200 CC_LOSS_COM MUNICATION Cascade System Managing cascade control lost communication with one of the depending connection between cascaded boilers is interrupted or wiring is broken Check wiring between boiler or distance between boilers is to big...

Страница 92: ...rk for cascade the communication busses must be parallel linked together The managing boiler uses the AL bus connection 20 21 for the cascade The depending boilers must be connected to the managing boiler on the 10 11 connection terminals It is important that the power on the 10 11 connection terminals on all dependent boilers is switched to the OFF position see also 15 2 1 All boilers in the casc...

Страница 93: ... Module Cascade Settings Change burner address into Managing or Dependent Now select in parameter 147 how many boilers units are in the cascade Boiler address Boiler Operation 0 default 1 2 3 4 Standalone burner 1st boiler managing 2nd boiler depending 3rd boiler depending 4th boiler depending Function of sensor input terminal 3 4 No function System sensor No function No function No function 16 16...

Страница 94: ... Cascade CH setpoint adaption When the system temperature is not high enough the setpoint for all boilers will be adjusted The boiler setpoint will be increased when the system temperature drops below Cascade_Setpoint and decreased when it rises above Cascade_Setpoint temperature Dependent Boiler The CH mode for the cascade is defined by the setting of the managing boiler CH mode settings on depen...

Страница 95: ...a given interval indicated with parameter Minute_Switch_Priority As soon as the interval has expired the priority switches to CH demand The interval time will be reloaded and priority will switch again after the interval is over 1 CH The priority is permanently given to CH Demand 2 DHW The priority is permanently given to DHW Demand Relevant variables Specific Parameters Level Default Value Range ...

Страница 96: ... degrees below the Cascade_Setpoint the burners are started at intervals of Start_Next_Depending_Delay for example 200 seconds Stopping Burners If T_System is Hyst_Up_Stop_Burner degrees above the Cascade_Setpoint the burners are stopped at intervals of Stop_Next_Depending_Delay for example 180 seconds Power balance When T_System is between Hyst_Down_Start_Burner and Hyst_Up_Stop_Burner a power ba...

Страница 97: ...st_Up_Stop_All Stop Burner Diff 2 Installer 8 ºC 14 ºF 0 30 ºC 0 54 ºF Hyst_Down_Quick_Start Start Burner Diff in short time 2 Installer 10 ºC 18 ºF 0 20 ºC 0 36 ºF Hyst_Up_Quick_Stop Stop Burner Diff in short time 2 Installer 6 ºC 11 ºF 0 20 ºC 0 36 ºF 15 2 6 CASCADE POWER BALANCE MODE Several different power control modes can be selected to operate the cascade system Power mode 0 Power control d...

Страница 98: ...l PID controlled depending in burn state Power Stop_Power_Threshold The managing burner releases another burner for PID control and waits for 3 min Stop_Next_Depending_Delay settable before another burner can be stopped Relevant variables Specific Parameters Level Default Value Range Power Mode 2 Installer 3 0 3 Start_Power_Threshold Threshold rate before starting the next burner Condition at leas...

Страница 99: ...lowing conditions When the average burner power of all depending burners is over the set start rate for the next burner o Sum of burner power of all depending Start_Power_Threshold depending in burn Burner shut down The last started burner will be stopped under the following conditions When the average burner power of all depending burners is under the set stop rate for the next burner o Sum of bu...

Страница 100: ...parameter First_Depending_To_Start is automatically updated to the next depending When boiler rotation is disabled the parameter First_Depending_To_Start is reset to 0 When the First_Depending_To_Start is manually changed the control will clear all demand of the cascade control After this is will start cascade demand generation with the new selection for First_Depending_To_Start 15 3 1 NEXT DEPEND...

Страница 101: ...e setting Emergency_Mode is enabled the control can go into emergency mode when the system sensor status is open or shorted The managing boiler display may show that the system is in emergency mode In emergency mode the system setpoint is set to the Emergency_Setpoint settable via installer menu and all cascaded boilers are allowed to start burning on this setpoint Loss of cascade communication Th...

Страница 102: ...Max_Temp_Error 7 Low water cut off 1 error test Simulates the LWCO_1_ Error 8 Low water cut off 2 error test Simulates the LWCO_2_ Error Before running the system test modes first check if the heat can also be dissipated Note that during this mode the supply temperature can be raised above 95 ºC 203 ºF When this temperature is reached the boiler will switch OFF When the supply temperature cools do...

Страница 103: ...l heating system Filling water Do not use any additives for the water of the central heating system except glycol The pH value of the water should be more than 5 If this pH value is less please contact the supplier Ensure that any used plastic pipes are oxygen diffusion proof in accordance with DIN 4726 4729 If not make sure that the boiler circuit is separated from the heating circuit by a plate ...

Страница 104: ...he gas safety valve for this measurement In chapter 18 1 2 the position of the pressure nipple 3 is shown Min and max gas supply pressures 17 6 Firing for the first time After the commissioning of the boiler and the described previous actions the boiler display will show this screen This screen is active during power up and will remain active until communication with the main Control has been esta...

Страница 105: ... Prior to adjustments follow the procedure in 18 3 The fan has been replaced The flue gas check valve has been replaced In any of the cases described always check the gas air ratio of the combustion figure CO2 at maximum and minimum input First set the boiler at maximum load and subsequently at minimum load and repeat if necessary adjustments at maximum load influence values at minimum load and vi...

Страница 106: ...Location of the setting screws High Fire venturi adjustment screw use hex key 4 mm 5 32 Allen wrench Low Fire gas valve adjustment screw Torx T40 High Fire screw 2 Low Fire screw 1 Low Fire screw 1 High Fire screw 2 Gas pressure nipple 3 Gas Pressure nipple 3 ...

Страница 107: ...he system test automatically stops after 10 minutes after this the system continues with normal demand handling When the system test mode is changed during an active system test the 10 minute timer is restarted Procedure 2 adjust at Low Fire Carry out the next steps 1 Press UP DOWN multiple times to select Low Power Test State Low Power After about 10 seconds the boiler burns at low fire 2 Measure...

Страница 108: ...ter 138 will need to be changed on the S CBX boiler to complete the conversion from natural gas to propane LPG There is one main PCB board that does the S CBX 85 105 on both natural gas and LPG supply and one board that does the S CBX 125 155 on both natural gas and LPG Detailed below Option 2 Model Natural Gas Propane S CBX 85 PCB 1 PCB 1 S CBX 105 PCB 1 PCB 1 S CBX 125 PCB 2 PCB 2 S CBX 155 PCB ...

Страница 109: ...nd gas combination valve can now be separated The orifice is to be placed between venturi and gas combination valve The rounded side of the orifice must be on the side of the gas combination valve The orifice must be mounted into the gas access of the venturi and secured with the rubber gasket 4 Venturi and gas combination valve now can be reconnected 5 Remount the gas combination valve and the ve...

Страница 110: ...e PCB 1 Boiler type Fuel Supply appliance type S CBX 85 Natural Gas 50 S CBX 85 Propane LPG 51 S CBX 105 Natural Gas 52 S CBX 105 Propane LPG 53 PCB 2 Boiler type Fuel Supply appliance type S CBX 125 Natural Gas 50 S CBX 125 Propane LPG 51 S CBX 155 Natural Gas 52 S CBX 155 Propane LPG 53 Confirmation After this perform CO2 adjustments according to the procedures in 18 2 using the values in table ...

Страница 111: ...n top of boiler Condensate Drain Check the level of the heat exchanger It must have a slight angle from the rear to ensure that the condensate drains from the heat exchanger YES NO Condensate trap from package installed according installation manual YES NO Inside diameter of drain piping mm inch Is there a definite air gap between the condensate trap and the connection to drain pipe YES NO Total d...

Страница 112: ...s supply Type of Gas from installation Is gas isolation valve installed under boiler according to installation manual YES NO Which diameter gas isolation valve is installed Gas piping inside diameter Gas piping material if possible specify mark type Gas piping flexible YES NO YES NO Gas piping inside structure e g smooth corrugated Measured Gas pressure Gas valve Static Measured Gas pressure Gas v...

Страница 113: ...ormation Serial number Date and time of maintenance Name of maintenance engineer Which parts were exchanged during maintenance Which settings software were changed during maintenance Special remarks findings Future aspects that need extra attention Additional aspects measurement reports complaints by the end user lock out codes etc Static Gas Pressure CO2 O2 at high fire Gas Pressure at high fire ...

Страница 114: ...make more space to dismantle the complete burner unit pull down the burner controller unit To remove this part for an internal heat exchanger check remove the six M6 nuts the ignition cable and the thermal fuse cables Close the gas tap under the boiler and loosen the gas coupling by untighten the swivel joint under the gas valve Remove the air intake pipe from the venturi After this take out the c...

Страница 115: ...nd the electrodes into the right position Notice the electrodes undergo high temperatures therefore the electrodes become hard and are difficult to bend While bending used electrodes they might break or burst Check the electrode after bending for any tear crack and signs of rust When they are damaged in any manner or rusty replace the electrode Also replace the electrode when there is a crack in t...

Страница 116: ...rner door s thermostat with a torque of 2 Nm Reconnect the wiring Burner door gaskets If any part of a gasket has discoloured changed texture or hardened then the rubber has cured and or has damages these gaskets must be replaced Notice Only use the gaskets that are supplied by the boiler manufacturer Burner door gasket replacement Remove the old gasket Place a new gasket in its groove Respect the...

Страница 117: ...e electrodes Remove the braids by sliding under the periphery a thin tool to loosen the braids and remove it Remove and clean the residues of the braids and silicone glue Put a thin string of glue silicone temperature resistant in the seal housing Loctite 5366 or Ottoseal S17 Engage the high temp braided rope and place it in contact of the glue and press the braids Reinstall electrodes Picture 19 ...

Страница 118: ...otective film is not sticking anymore on the rear side of this insulation disk To prevent debris from falling in between the coils place a sheet e g paper on the bottom beneath the disk Make the insulation wet by spraying water over it This in order to keep airborne dust to a minimum With a knife cut a cross in the insulation disk avoiding the central insert on the back not visible Make a square c...

Страница 119: ...ate Trap Disassemble the condensate trap and clean every part of it Check the condensate trap connection of the heat exchanger for any blocking or pollution and clean it if necessary Check the functioning of the condensate trap by pouring clean tap water in the boiler combustion chamber when burner door is removed This water will exit the heat exchanger by the condensate trap Notice don t wet the ...

Страница 120: ...ected checked and replaced Make sure that all these components are mounted correctly before commissioning the boiler again Cleaning the combustion chamber and heat exchanger with acid or alkali products is prohibited 19 2 1 MOUNTING THE BURNER DOOR IMPORTANT Before mounting the burner door make sure that its gaskets and insulation are in excellent shape If any signs of damage or ageing are present...

Страница 121: ...ing Record gas pressure and note pressure drop upon start up Record CO2 at high and low fire Visual and Temperature Do visual inspection of all system components and verify programmed temperature settings Connections Check wire connections and make sure they are tight Combustion chamber Check burner tube and combustion chamber coils Clean with nylon brush and vacuum Avoid touching white ceramic fi...

Страница 122: ...d user The user should be made familiar with all safety precautions of the boiler and the installation The user should be instructed that service and maintenance of the boiler is required every twelve months Regular service and maintenance is essential for a safe and proper operation of the boiler Hand over the documents supplied with the boiler ...

Страница 123: ...Connections Name Wire terminal RT Room thermostat 12 13 FS Flow temperature sensor 3 4 LLH Low loss header High Voltage Connections P1 boiler pump 4 PE 5 P3 system heating pump 6 PE 7 System Example 2 Low Voltage Connections Name Wire terminal OS outdoor temperature sensor 1 2 FS Flow temperature sensor 3 4 LLH Low loss header High Voltage Connections P1 boiler pump 4 PE 5 P3 system heating pump 6...

Страница 124: ...ing pump 6 PE 7 System Example 4 Low Voltage Connections Name Wire terminal RT Room thermostat 12 13 FS flow temperature sensor 3 4 OS outdoor temperature sensor 1 2 ST Tank thermostat or sensor 5 6 LLH low loss header T DHW indirect Tank High Voltage Connections P1 boiler pump 4 PE 5 P3 System heating pump 6 PE 7 DV diverter valve 3 way valve 1 2 3 PE P3 P1 HEATING ZONE BOILER OS RT FS LLH DV T L...

Страница 125: ...mary pump 2 3 PE P3 System heating pump 6 PE 7 System Example 6 Low Voltage Connections Name Wire terminal RT Room thermostat 12 13 OS outdoor temperature sensor 1 2 FS flow temperature sensor 3 4 SNV non return valve low resistance type LLH low loss header High Voltage Connections P1 boiler pump 4 PE 5 P3 System heating pump 6 PE 7 LLH FS RT P3 P1 HEATING ZONE BOILER OS ST P2 SNV SNV T P1 P1 P1 P...

Страница 126: ...thermostat or sensor 5 6 T DHW indirect Tank SNV non return valve low resistance type LLH low loss header High Voltage Connections P1 boiler pump 4 PE 5 P2 HWS primary pump 2 3 PE P3 System heating pump 6 PE 7 P1 P1 P1 P1 P3 LLH FS OS RT SNV SNV SNV SNV BOILER 1 managing HEATING ZONE BOILER 2 depending 1 BOILER 3 depending 2 BOILER 4 depending 3 T P2 SNV SNV ST ...

Страница 127: ...tion service or maintenance can cause property damage personal injury exposure to hazardous materials or loss of life Installation and service must be performed by a qualified installer service agency or the gas supplier who must read and follow the supplied instructions before installing servicing or removing this boiler This boiler contains materials that have been identified as carcinogenic or ...

Страница 128: ...tatus overview when directly setting Actual setpoint or DHW setpoint Left Return to previous menu item or Status overview Up Directly select Actual setpoint of DHW setpoint in the Status overview push RIGHT to confirm and use UP or DOWN to adjust value Down Directly select Actual setpoint of DHW setpoint in the Status overview push RIGHT to confirm and use UP or DOWN to adjust value Enter Confirm ...

Страница 129: ...ing and the following screen appears The De Air sequence is a safety function that starts at every power up and is used to remove the air from the heat exchanger The De Air sequence takes around 14 minutes to complete It can be cancelled by pressing the Enter button for over 5 seconds After completion or manual ending the De Air sequence one of the following Status overview screens appears OR Icon...

Страница 130: ...ht part of the PB screen is used to display the error or alert 22 8 2 CHANGING THE DHW SETPOINT DIRECTLY Only applicable if this function is available Press the UP or DOWN button to select the mode 57 0 C is just an example of a possible temperature value Use the left right buttons to move the sign to the front of the temperature digits Use UP DOWN buttons to increase decrease the setpoint Press t...

Страница 131: ...ected by a password are only accessible by the installer Passwords are always customer specific and for safety reasons will be provided to the installer only The following menu items require a password Menu item Location inside menu Start up Settings Settings General Settings Other Settings Startup Settings Boiler Parameters Settings Boiler Settings Boiler Parameters Module Cascade Settings Settin...

Страница 132: ...e C F DHW Temperature Actual DHW temperature C F DCW Temperature Actual DCW temperature C F Outside Temperature Actual outside temperature C F Flue Temp Actual flue gas temperature C F Flue 2 Temp Actual flue gas 2 temperature C F System Temperature Actual system temperature C F 0 10 V Input Actual 0 10 V input value V Flowrate Actual DHW flowrate l min RT Input Actual RT input status open closed ...

Страница 133: ... 12 12 UNIT TYPE Menu Parameter Description Value Unit Metric C bar Select Metric units C bar Imperial F psi Select Imperial units F psi 22 12 13 DATE TIME Menu Parameter Description Value Unit Date Set the current date dd mm yyyy Time Set the current time hh mm Time Zone Settings Enter the time zone settings menu Display Settings Enter the display settings menu 22 12 14 TIME ZONE SETTINGS Menu Pa...

Страница 134: ...errors will be stored in the error log An error will be logged with a Real Time Clock time stamp date and time when the error was detected and a boiler ID of the boiler on which the error was detected Note the error log is a completely different error logging mechanism than the one used by the burner controller itself Therefore the error log is different from the internal error history of the burn...

Страница 135: ... a service moment will be counted and the Service overdue counter will be stored in the log history It is possible to reset the Service reminder counters before the Service reminder was actually set This should be done when the appliance was serviced before the Service reminder was active This means an overdue counter of 0 hours will be stored on the log which makes sense because the service was n...

Страница 136: ...power limited by the CH max power parameter 6 High limit error test Simulates the Max_Temp_Error 7 Low Water Cut Off 1 error test Simulates the LWCO_1_ Error 8 Low Water Cut Off 2 error test Simulates the LWCO_2_ Error Before running the system test modes first check if the heat can also be dissipated Note that during this mode the supply temperature can be raised above 95 ºC 203 ºF When this temp...

Страница 137: ......

Страница 138: ...22 F 01276 685405 E info strebel co uk I www strebel co uk STREBEL LTD RESERVE THE RIGHT TO CHANGE ANY SPECIFICATIONS ON THIS BOILER RANGE WITHOUT NOTICE Further information on our complete product range is available from our website CAST IRON CONDENSING STEEL SHELL WATER HEATERS RENEWABLES FLUES ACCESSORIES ...

Отзывы: