35
C33
Closed
Air supply from
outside
* Flue terminal at the roof.
* Air supply inlet and flue gas outlet located
at the same air pressure zone
(a combined roof terminal e.g.).
See: Typical examples - example B
C63 - example
Closed
Air supply
from outside
* Appliance sold without flue/air-inlet ducts
* The flue gas parts are not part of the
boiler. The boiler is intended to be
connected to a separately approved and
marketed system for the supply of
combustion air and discharge of
combustion products.
Condensate is allowed to go to the boiler.
* Air supply inlet and flue gas outlet not at
opposite walls
* Technical data:
nominal T
flue gas
85 °C
nominal Q
fluegas
see 3.2.1
1)
maximum T
fluegas
90 °C
min. load T
fluegas
35 °C
min. load Q
fluegas
see 3.2.1
1)
nominal % CO
2
see 3.2.1
1)
max. allowed draft
70 Pa
max. pressure drop
inlet-outlet
200 Pa
max T
air supply
40 °C
max recirculation
10 %
1) technical specifications datasheet
See: Typical examples - example A
Concentric roof terminal
concentric/
parallel adaptor
roof terminal
roof terminal
Flue outlet
Air inlet