4.2 Boiler settings
min. max. Default unit
Access
level
Description:
4.2.1 Boiler Parameters
installer
Enter the Boiler Parameters
menu
4.2.2 Module Cascade
Settings
installer
Enter the Module Cascade
Settings menu
4.2.3 Boiler Cascade
Settings
installer
Enter the Boiler Cascade
Settings menu
5 System test
min. max. Default unit
Access
level
Description:
Test State
off
installer
set test state (for adjusting CO2
level's)
Fan speed
xxxx
rpm
installer
read out fan speed
Ionization
xxxx
uA
installer
read out flame signal
4.2.1 Boiler parameters
min. max. Default unit
Access
level
Description:
Displ
ay
nr:
CH mode
0
5
1
#
Installer Set the CH mode
1
CH Setpoint
20
90
85
⁰
C
Installer Set the CH setpoint
3
Calc. Setp. Offset
-10
10
0
⁰
C
Installer Set the offset for CH mode
1 / 2 calculated setpoint
185
Boiler Pump Overrun
0
900
120
sec.
Installer Set the post-circulation time
for the boiler/CH pump
5
CH Hysteresis Up
2
40
3
⁰
C
Installer Set the CH hysteresis up
7
CH Hysteresis Down
2
20
5
⁰
C
Installer Set the CH hysteresis down 112
Anti-Cycle Period
10
900
180
sec.
Installer Set the burner anti-cycling
period
9
Anti-Cycle Temp. Diff.
0
20
16
⁰
C
Installer Set the burner anti-cycling
differentia
10
Design Supply Temp.
4
90
85
⁰
C
Installer Set CH setpoint when
outdoor temperature equals
Des. Outd. T.
19
Design Outdoor Temp.
-25
25
-5
⁰
C
Installer Set the outdoor
temperature at which CH
setpoint is set to Des.
Supply T.
20
Baseline Supply Temp
4
90
40
⁰
C
Installer Set CH setpoint when
outdoor temperature equals
Bas. Outd. T.
21
Baseline Outdoor Temp
0
30
20
⁰
C
Installer Set the outdoor
temperature at which CH
setpoint is set to Bas.
Supply T.
22
Design Supply Min. Limit
4
82
20
⁰
C
Installer Set the outdoor reset curve
minimum setpoint
23
Design Supply Max. Limit 27
90
90
⁰
C
Installer Set the outdoor reset curve
maximum setpoint
24
Warm Weather Shutdn
0
35
22
⁰
C
Installer Set outdoor temperature
above which CH demand is
blocked
25
Boost Temp Increment
0
30
0
⁰
C
Installer Set the setpoint boost
function temperature
increment
26
Boost Time Delay
0
120
20
min.
Installer Set the setpoint boost
function delay time
27
Night Setback Temp.
0
30
10
⁰
C
Installer Set the CH setpoint night
setback temperature
28
DHW Mode
0
8
0
#
Installer Set the DHW mode
35
DHW Tank Hyst. Down
0
10
5
⁰
C
Installer Set the DHW tank
hysteresis down
36
DHW Tank Hyst. Up
0
10
5
⁰
C
Installer Set the DHW tank
hysteresis up
37