Change the Appliance Type.
1. From status screen, press MENU. → "Central Heating/ Information/ Settings/ System Test"
2. Press UP/DOWN ↑↓ to select "Settings" and press CONFIRM
3. Press UP/DOWN ↑↓ to select "Boiler Settings" and press CONFIRM
4. Enter password level 2 by pressing UP/DOWN ↑↓ and LEFT ← /RIGHT→
5. Press UP/DOWN ↑↓ to select "Boiler parameter" and press ENTER
6. Press UP/DOWN ↑↓ to select parameter "(138) Appliance type" and press ENTER
7. Press UP/DOWN ↑↓ to change the appliance type according table below.
8. To return to the status screen, press ESCAPE or MENU 3 times, or RESET once.
PCB 1
Boiler type
Fuel Supply
appliance type
S-CBX 85
Natural Gas
50
S-CBX 85
Propane (LPG)
51
S-CBX 105
Natural Gas
52
S-CBX 105 Propane (LPG)
53
PCB 2
Boiler type
Fuel Supply
appliance type
S-CBX 125
Natural Gas
50
S-CBX 125 Propane (LPG)
51
S-CBX 155
Natural Gas
52
S-CBX 155 Propane (LPG)
53
Confirmation
After this, perform CO
2
adjustments according to the
procedures in 18.2, using the values in table 18.1. When
finished, apply the corresponding sticker at the appropriate
position in the boiler and mark the box for the used gas type.
Also mark the box, indicating that the correct value has been
set for the appliance type.
It's possible to improve the ignition spark by using an external ignition coil. Available on request,
see the accessories paragraph