91
Lockout
code
Error
Description
Cause
Solving
155 WD_CONFIG_E
RROR
Watchdog fan configuration
setting error
wrongly program-
med PCB or PB
reset PCB or replace PCB
and or display unit
162 FILL_WARNING Error is generated
immediately when the
pressure drops below
Minimal Pressure. Demand
has stopped, but no error
needs to be stored at this
time.
The water
pressure is below
the minimum
pressure level
refill the system until the
pressure is above 1 Bar or
14.5 PSI
164 LOWEXFLOW_
PROTECTION
Flow is too low, demand
needs to be stopped with
fan at ignition speed*, but
no error needed to be
stored at this time
not enough water
flow through heat
exchanger
Check functioning of the
pump. Check/open all
valves that might restrict
the water flow through the
unit.
Check for an external
system pump that
influences flow through the
unit.
Check if the system
resistance exceeds the
spare capacity of the unit
pump.
165 VSUPPLY_TOO
_LOW
Main supply voltage too low
for more than 60 seconds
dip in power
supply to boiler
check power supply
166 VSUPPLY_TOO
_HIGH
Main supply voltage too
high for more than 60
seconds
peak in power
supply to boiler
check power supply
14.5 Warnings
Error no.
Error
Description
Cause
Solving
200 CC_LOSS_COM
MUNICATION
Cascade System: Managing
cascade control lost
communication with one of
the depending.
connection
between cascaded
boilers is
interrupted or
wiring is broken
Check wiring between boiler
or distance between boilers
is to big
202 APP_SELECTIO
N_ERROR
Unknown appliance model
selected
wrongly
programmed
parameters
replace PCB
203 CC_LOSS_BOIL
ER_COMM
Dual Cascade System:
Managing cascade control
lost communication with one
of the depending.
connection
between cascaded
boilers is
interrupted or
wiring is broken
Check wiring between boiler
or distance between boilers
is to big
204 OUTDOOR_
WRONG
T_Outdoor sensor measures
open/shorted
Faulty outdoor
sensor or not
connected or
wrong CH-mode
programmed
check connection to PCB or
check resistance NTC
sensor or change CH-mode
205 T_SYSTEM_
WRONG
T_System sensor measures
open/shorted
Faulty system
sensor or not
connected
check connection to PCB or
check resistance NTC
sensor
206 T_CASCADE_W
RONG
T_Cascade sensor
measures open/shorted
Faulty cascade
sensor or not
connected
check connection to PCB or
check resistance NTC
sensor