Montage- und Anschlussanleitung / Funk-Empfänger
Mounting and wiring instructions / Wireless receiver
Instructions de montage et de câblage / Récepteur sans fil
Istruzioni di montaggio e collegamento / Ricevitore wireless
Instruções de montagem e instalação / Receptor sem fio
Инструкция по монтажу и подключению / Радиоприемник
//
RF Rx EN868 TCP/IP / RF Rx SW868/SW915/SW917/SW922 TCP/IP V2
14 / 52
English
Example EnOcean® telegram
Data: (hex
stream,
29 byte)
0000: 41 35 35 41 30 42 30 35 33 30 30 30 30 30 30 30
0010: 30 30 31 30 36 41 31 44 33 30 30 37 0a
Data:
(ASCII, 29
charaters)
A55A0B053000000000106A1D3007[LF]
Byte
0 1
2
3
4 5 6 7
8 9 10 11
12
13
Meaning
Sync
LEN
ORG
Data
ID
Status
CRC
HEX code
A55A
0B
05
30000000
00106A1D
30
07
*interface definition EnOcean® at http://www.enocean.com!
Error telegram
If the Gateway detects an error, it attempts to transmit an error tele-
gram to the configurated receiver. An error telegram always starts
with »E:«, followed by the error text and a terminating »[LF]«.
Example telegram
Data: (Hex
stream,
29 byte)
0000: 45 3a 20 54 43 50 20 6d 65 73 73 61 67 65 20 64
0010: 69 63 61 72 64 65 64 20 28 73 6f 63 6b 65 74 20
0020: 6e 6f 74 20 6f 70 65 6e 29 20 6c 69 6e 65 3a 20
0030: 41 4c 4c 00 0a
Data:
(ASCII, 29
characters)
E: TCP message discarded (socket open) line: ALL
[LF]
Troubleshooting
Description
Cause
Solution
Power LED (green)
off
No power supply;
internal power sup-
ply defective
Check power supply;
replace module
Power LED (green)
flashes
Hardware defect
Replace module
LED network link
(green) off
No or defective net-
work cable;
network receiver not
active
Replace network
cable;
turn on/check net-
work router or switch
Configuration
website can not be
indicated
Gateway IP and PC
IP not in the same
address range;
website already
opened
Adapt PC IP;
reset Gateway to
initial setting;
terminate access
(close browser)
To test the function, a ModbusTCP tool such as the freely available
QModMaster is useful (https://sourceforge.net/projects/qmodmaster/),
e.g. on a laptop in the network of the PLC and the Gateway.
The IP address and port of the Gateway must be set in the ModbusTCP
settings. 2000 was selected as the start address in order to read out all
40 possible switches at once. After clicking on the »Connect« and
»Scan« icons (marked in blue), the tool cyclically retrieves the switch
data. The screenshot shows switch 2 as pressed. All other switches
have not been pressed since the Gateway was restarted.
Wireless telegram
The wireless telegram included in the TCP/UDP datagram is transmit-
ted in hexadecimal coding as an ASCII string with a terminating »[LF]«
control character (line feed). In special cases it is possible that one da-
tagram contains several wireless telegrams separated by »[LF]«. This
is possible especially after an ethernet transmission error when at this
particular time of the repeated transmission further wireless tele-
grams have already been received by the Gateway.
Example sWave® telegram
Data: (hex
stream,
25 byte)
0000: 30 32 30 41 34 32 33 35 44 39 42 46 31 30 37 45
0010: 46 30 30 30 30 30 39 39 0a
Data:
(ASCII, 25
characters)
020A4235D9BF107EF0000099[LF]
Byte
0
1
2
3 4 5
6
7
8
9
10
11
Mean-
ing
Pre-
amble
LEN
MODE
ADR
Data #1
RSSI
Data #2
Bat
Sensor
Check-
sum
HEX
code
02
0A
42
35D9BF
10
7E
F0
00
00
99
*interface definition sWave® on request!