SSI700 User Manual Description of Function Codes
www.ssinverter.info
Value
Function
Range (Corresponding to Pulse or Analog Output Range
0.0%–100.0%)
13
Motor rotational speed
0 to rotational speed corresponding to maximum output
frequency
14
Output current
0.0–1000.0 A
15
Output voltage
0.0–000.0 V
16
reserved
Property
Default
Setting
Range
Parameter
Name
Function
Code
Group P5: Output Terminals
☆
50.00
kHz
0.01–100.00 kHz
Maximum FMP output
frequency
P5-09
If the FM terminal is used for pulse output, this parameter is used to set the maximum
frequency of pulse output.
Property
Default
Setting
Range
Parameter
Name
Function
Code
Group P5: Output Terminals
☆
0.0%
-100.0%–100.0%
AO1 offset coefficient
P5-10
☆
1.00
-10.00–10.00
AO1 gain
P5-11
These parameters are used to correct the zero drift of analog output and the output
amplitude deviation. They can also be used to define the desired AO curve.
If "b" represents zero offset, "k" represents gain, "B" represents actual output, and "A"
represents standard output, the actual output is: B = kA + b.
The zero offset coefficient 100% of AO1 corresponds to 10 V (or 20 mA). The standard
output refers to the value corresponding to the analog output of 0 to 10 V (or 0 to 20 mA)
with no zero offset or gain adjustment.
For example, if the analog output is used as the running frequency, and it is expected that
the output is 8 V when the frequency is 0 and 3 V at the maximum frequency, the gain
shall be set to -0.50, and the zero offset shall be set to 80%.
Property
Default
Setting
Range
Parameter
Name
Function
Code
Group P5: Output Terminals
☆
0.0s
0.0–3600.0s
FMR output delay time
P5-17
☆
0.0s
0.0–3600.0s
Relay output delay time
P5-18
☆
0.0s
0.0–3600.0s
DO1 output delay time
P5-20
These parameters are used to set the delay time of output terminals FMR, relay, DO1
from status change to actual output.
Property
Default
Setting
Range
Parameter
Name
Function
Code
Group P5: Output Terminals
☆
00000
Unit's digit (FMR valid mode)
DO valid mode selection
P5-22
0: Positive logic
1: Negative logic
Ten's digit (Relay valid mode)
0, 1 (same as FMR)
Thousand's digit (DO1 valid
mode)
0, 1 (same as FMR)
It is used to set the logic of output terminals FMR, relay, DO1.
Содержание SSI700
Страница 1: ......
Страница 3: ...Safety Information and Precautions...
Страница 7: ...Product Information...
Страница 12: ...Mechanical and Electrical Installation...
Страница 19: ...Operation Display and Application Examples...
Страница 42: ...Function Code Table...
Страница 64: ...Description of Function Codes...
Страница 131: ...EMC...
Страница 137: ...Selection and Dimensions...
Страница 141: ...Maintenance and Troubleshooting...