SSI700 User Manual Description of Function Codes
www.ssinverter.info
Function Description
Value
Parameter
Name
Function
Code
Two-line 1
2
Terminal command mode
P4-11
Forward RUN (FWD)
1
DI1 function selection
P4-00
Reverse RUN (REV)
2
DI2 function selection
P4-01
Three-line control
3
DI3 function selection
P4-02
Figure 6-9 Setting of three-line mode 1
As shown in the preceding figure, if SB1 is ON, the AC drive instructs forward rotation
when SB2 is pressed to be ON and instructs reverse rotation when SB3 is pressed to be
ON. The AC drive stops immediately after SB1 becomes OFF. During normal startup and
running, SB1 must remain ON. The AC drive's running state is determined by the final
actions on SB1, SB2 and SB3.
• 3: Three-line mode 2
In this mode, DI3 is RUN enabled terminal. The RUN command is given by DI1 and the
direction is decided by DI2. The parameters are set as below:
Function Description
Value
Parameter
Name
Function
Code
Two-line 2
3
Terminal command mode
P4-11
Forward RUN (FWD)
1
DI1 function selection
P4-00
Reverse RUN (REV)
2
DI2 function selection
P4-01
Three-line control
3
DI3 function selection
P4-02
Figure 6-10 Setting of three-line mode 2
K
RUN
command
0
Forward
RUN
1
Reverse
RUN
Содержание SSI700
Страница 1: ......
Страница 3: ...Safety Information and Precautions...
Страница 7: ...Product Information...
Страница 12: ...Mechanical and Electrical Installation...
Страница 19: ...Operation Display and Application Examples...
Страница 42: ...Function Code Table...
Страница 64: ...Description of Function Codes...
Страница 131: ...EMC...
Страница 137: ...Selection and Dimensions...
Страница 141: ...Maintenance and Troubleshooting...