SSI700 User Manual Description of Function Codes
www.ssinverter.info
Default
Setting
Range
Parameter
Name
Function
Code
Group 9: Fault and Protection
00000
Unit's digit (Motor overload, OL1)
Fault protection
action selection
1
P9-47
0: Coast to stop
1: Stop according to the stop mode
2: Continue to run
Hundred's digit (Power output phase loss, LF)
Same as unit's digit
Thousand's digit (External equipment fault, EF)
Same as unit's digit
Ten thousand's digit (Communication fault, CE)
Same as unit's digit
00000
Ten's digit (EEPROM read-write fault, EP)
Fault protection
action
selection 2
P9-48
0: Coast to stop
1: Stop according to the stop Mode
Ten thousand's digit (Accumulative running time
reached)
Same as unit's digit in P9-47
00000
Hundred's digit (Accumulative power-on time
reached,UT)
Fault protection
action
selection 3
P9-49
Same as unit's digit in P9-47
Thousand's digit (Load becoming0)
0: Coast to stop
1: Stop according to the stop mode
2: Continue to run at 7% of rated motor frequency
and resume to the set frequency if the load
recovers
Ten thousand's digit (PID feedback lost during
running, PD)
Same as unit's digit in P9-47
00000
Unit's digit (Too large speed deviation)
Fault protection
action selection
4
P9-50
Same as unit's digit in P9-47
Ten's digit (Motor over-speed)
Same as unit's digit in P9-47
Hundred's digit (Initial position fault)
Same as unit's digit in P9-47
If "Coast to stop" is selected, the AC drive displays fault and directly stops.
• If "Stop according to the stop mode" is selected, the AC drive displays D** and stops
according to the stop mode. After stop, the AC drive displays fault.
• If "Continue to run" is selected, the AC drive continues to run and displays D**. The
running frequency is set in P9-54.
Default
Setting
Range
Parameter
Name
Function
Code
0
0: Current running frequency
1: Set frequency
2: Frequency upper limit
3: Frequency lower limit
4: Backup frequency upon abnormality
Frequency selection for
continuing to run upon fault
P9-54
100.0%
0.0%–100.0% (maximum frequency)
Backup frequency upon
abnormality
P9-55
If a fault occurs during the running of the AC drive and the handling of fault is set to
"Continue to run", the AC drive displays D** and continues to run at the frequency set in
P9-54.
The setting of P9-55 is a percentage relative to the maximum frequency.
Содержание SSI700
Страница 1: ......
Страница 3: ...Safety Information and Precautions...
Страница 7: ...Product Information...
Страница 12: ...Mechanical and Electrical Installation...
Страница 19: ...Operation Display and Application Examples...
Страница 42: ...Function Code Table...
Страница 64: ...Description of Function Codes...
Страница 131: ...EMC...
Страница 137: ...Selection and Dimensions...
Страница 141: ...Maintenance and Troubleshooting...