SSI700 User Manual Description of Function Codes
www.ssinverter.info
Property
Default
Setting
Range
Parameter
Name
Function
Code
Group P8: Auxiliary Functions
☆
75°C
0–100°C
Module temperature
threshold
P8-47
When the heatsink temperature of the AC drive reaches the value of this parameter, the
corresponding DO becomes ON, indicating that the module temperature reaches the
threshold.
Property
Default
Setting
Range
Parameter
Name
Function
Code
Group P8: Auxiliary Functions
☆
0
0: Fan working during running
1: Fan working continuously
Cooling fan control
P8-48
It is used to set the working mode of the cooling fan. If this parameter is set to 0, the fan
works when the AC drive is in running state. When the AC drive stops, the cooling fan
works if the heatsink temperature is higher than 40°C, and stops working if the heatsink
temperature is lower than 40°C.
If this parameter is set to 1, the cooling fan keeps working after power-on.
Property
Default
Setting
Range
Parameter
Name
Function
Code
Group P8: Auxiliary Functions
☆
0.00Hz
Dormant frequency (P8-51) to
maximum frequency (P0-10)
Wakeup frequency
P8-49
☆
0.0s
0.0–6500.0s
Wakeup delay time
P8-50
☆
0.00Hz
0.00 Hz to wakeup frequency
(P8-49)
Dormant(Sleeping)
frequency
P8-51
☆
0.0s
0.0–6500.0s
Dormant(Sleeping)
delay time
P8-52
These parameters are used to implement the dormant and wakeup functions in the water
supply application.
When the AC drive is in running state, the AC drive enters the dormant state and stops
automatically after the dormant delay time (P8-52) if the set frequency is lower than or
equal to the dormant frequency (P8-51).
When the AC drive is in dormant state and the current running command is effective, the
AC drives starts up after the wakeup delay time (P8-50) if the set frequency is higher than
or equal to the wakeup frequency (P8-49).
Generally, set the wakeup frequency equal to or higher than the dormant frequency. If the
wakeup frequency and dormant frequency are set to 0, the dormant and wakeup functions
are disabled.
When the dormant function is enabled, if the frequency source is PID, whether PID
operation is performed in the dormant state is determined by 11-28. In this case, select
PID operation enabled in the stop state (11-28 = 1).
Property
Default
Setting
Range
Parameter
Name
Function
Code
Group P8: Auxiliary Functions
☆
0.0 min
0.0–6500.0 min
Current running time
reached
P8-53
If the current running time reaches the value set in this parameter, the corresponding DO
becomes ON, indicating that the current running time is reached.
Содержание SSI700
Страница 1: ......
Страница 3: ...Safety Information and Precautions...
Страница 7: ...Product Information...
Страница 12: ...Mechanical and Electrical Installation...
Страница 19: ...Operation Display and Application Examples...
Страница 42: ...Function Code Table...
Страница 64: ...Description of Function Codes...
Страница 131: ...EMC...
Страница 137: ...Selection and Dimensions...
Страница 141: ...Maintenance and Troubleshooting...