SSI700 User Manual Description of Function Codes
www.ssinverter.info
Figure 6-22 Zero current detection
Property
Default
Setting
Range
Parameter
Name
Function
Code
Group P8: Auxiliary Functions
☆
200.0
%
0.0% (no detection)
0.1%–300.0% (rated motor
current)
Output overcurrent
threshold
P8-36
☆
0.00s
0.00–600.00s
Output overcurrent
detectiondelay time
P8-37
If the output current of the AC drive is equal to or higher than the overcurrent threshold
and the duration exceeds the detection delay time, the corresponding DO becomes ON.
The output overcurrent detection function is shown in the following figure.
Figure 6-23 Output overcurrent detection