SSI700 User Manual Description of Function Codes
www.ssinverter.info
Property
Default
Setting
Range
Parameter
Name
Function
Code
Group P0: Standard Function Parameters
★
10
0: Digital setting Preset P0-08,
UP/DOWN Can be modified.
(non-retentive at power failure)
1: Digital setting Preset P0-08,
UP/DOWN Can be modified.
(retentive at power failure)
2: AI1
3: AI2
4: Reserved
5: Pulse setting (DI5)
6: Multi-reference
7: Simple PLC
8: PID
9: Communication setting
10: Potentiometer key pad
Main frequency source
A selection
P0-03
It is used to select the setting channel of the main frequency. You can set the main
frequency in the following 10 channels:
•
0: Digital setting (non-retentive at power failure)
The initial value of the set frequency is the value of P0-08 (Preset frequency). You can
change the set frequency by pressing and on the operation panel (or using the
UP/DOWN function of input terminals). When the AC drive is powered on again after
power failure, the set frequency reverts to the value of P0-08.
•
1: Digital setting (retentive at power failure)
The initial value of the set frequency is the value of P0-08 (Preset frequency). You can
change the set frequency by pressing keys and on the operation panel (or using
the UP/DOWN function of input terminals).
When the AC drive is powered on again after power failure, the set frequency is the value
memorized at the moment of the last power failure.
Notes
that P0-23 (Retentive of digital setting frequency upon power failure) determines whether
the set frequency is memorized or cleared when the AC drive stops. It is related to stop
rather than power failure.
•
2: AI1 (0–10 V voltage input)
•
3: AI2 (0–10 V voltage or 4–20 mA current input, determined by jumper J8)
The frequency is set by analog input. The SSI700 control board provides two analog input
(AI) terminals (AI1, AI2).
The SSI700 provides five curves indicating the mapping relationship between the input
voltage of AI1, AI2 and the target frequency, three of which are linear (pointpoint)
correspondence and two of which are four-point correspondence curves. You can set the
curves by using function codes P4-13 to P4-27 and function codes in select curves for
AI1, AI2.
When AI is used as the frequency setting source, the corresponding value 100% of the
voltage/current input corresponds to the value of P0-10 (Maximum frequency).
•
5: Pulse setting (DI5)
The frequency is set by DI5 (high-speed pulse). The signal specification of pulse setting is
9–30 V (voltage range) and 0–100 kHz (frequency range). The corresponding value 100%
of pulse setting corresponds to the value of P0-10 (Maximum frequency).
Содержание SSI700
Страница 1: ......
Страница 3: ...Safety Information and Precautions...
Страница 7: ...Product Information...
Страница 12: ...Mechanical and Electrical Installation...
Страница 19: ...Operation Display and Application Examples...
Страница 42: ...Function Code Table...
Страница 64: ...Description of Function Codes...
Страница 131: ...EMC...
Страница 137: ...Selection and Dimensions...
Страница 141: ...Maintenance and Troubleshooting...