SSI700 User Manual Maintenance and Troubleshooting
www.ssinverter.info
Solutions
Possible Causes
Fault
SN
1: Reduce the carrier frequency
(P0-15).
2: Replace the fan and clean the
air filter.
3: Contact the agent or
Ssinverter for technical support.
1: The setting of carrier frequency is
too high.
2: The cooling fan is damaged, or
the air filter is blocked.
3: Components inside the AC drive
are damaged (thermal coupler or
others).
OH1 (module
overheat) fault is
reported
frequently.
5
1: Ensure the cable between the
AC drive and the motor is
normal.
2: Replace the motor or clear
mechanical faults.
3: Check and re-set motor
parameters.
1: Check the motor and the motor
cables.
2: The AC drive parameters are set
improperly (motor parameters).
3: The cable between the drive
board and the control board is in
poor contact.
4: The drive board is faulty.
The motor does
not rotate after the
AC drive runs.
6
1: Check and reset the
parameters in group P4.
2: Re-connect the external
signal cables.
3: Re-confirm the jumper bar
across OP and +24 V.
4: Contact the agent or
Ssinverter for technical support.
1: The parameters are set
incorrectly.
2: The external signal is incorrect.
3: The jumper bar across OP and
+24 V becomes loose.
4: The control board is faulty.
The DI terminals
are disabled.
7
1: Replace the encoder and
ensure the cabling is proper.
2: Replace the PG card.
3: Contact the agent or
Ssinverter for technical support.
1: The encoder is faulty.
2: The encoder cable is connected
incorrectly or in poor contact.
3: The PG card is faulty.
4: The drive board is faulty.
The motor speed
is always low in
CLVC mode.
8
1: Re-set motor parameters
or re-perform the motor
autotuning.
2: Set proper acceleration/
deceleration time.
3: Contact the agent or
Ssinverter for technical support.
1: The motor parameters are set
improperly.
2: The acceleration/deceleration
time is improper.
3: The load fluctuates.
The AC drive
reports overcurrent
and overvoltage
frequently.
9
1: Check whether the contactor
cable is loose.
2: Check whether the contactor
is faulty.
3: Check whether 24 V power
supply of the contactor is faulty.
4: Contact the agent or
Ssinverter for technical support.
The soft startup contactor is not
picked up.
“RL” is reported
upon power-on or
running.
10
Replace the control board.
Related component on the control
board is damaged.
is displayed upon
power-on.
11
Warranty Agreement
1. The warranty period of the product is 18 months (refer to the barcode on the
equipment). During the warranty period, if the product fails or is damaged under the
condition of normal use by following the instructions, Ssinverter will be responsible for free
maintenance.
2. Within the warranty period, maintenance will be charged for the damages caused by
the following reasons:
Содержание SSI700
Страница 1: ......
Страница 3: ...Safety Information and Precautions...
Страница 7: ...Product Information...
Страница 12: ...Mechanical and Electrical Installation...
Страница 19: ...Operation Display and Application Examples...
Страница 42: ...Function Code Table...
Страница 64: ...Description of Function Codes...
Страница 131: ...EMC...
Страница 137: ...Selection and Dimensions...
Страница 141: ...Maintenance and Troubleshooting...