SSI700 User Manual Description of Function Codes
www.ssinverter.info
Through complete motor auto-tuning, encoder phase sequence and current loop PI can
be obtained besides the parameters in P1-06 to P1-10.
Each time "Rated motor power" (P1-01) or "Rated motor voltage" (P1-02) is changed, the
AC drive automatically restores values of P1-06 to P1-10 to the parameter setting for the
common standard B series asynchronous motor.
If it is impossible to perform motor auto-tuning onsite, manually input the values of these
parameters according to data provided by the motor manufacturer.
Property
Default
Setting
Range
Parameter
Name
Function
Code
Group P1: Motor 1 Parameters
★
0
0: No auto-tuning
1: Asynchronous motor static
auto-tuning
2: Asynchronous motor complete
auto-tuning
Auto-tuning selection
P1-11
•
0: No auto-tuning
Auto-tuning is prohibited.
•
1: Asynchronous motor static auto-tuning
It is applicable to scenarios where complete auto-tuning cannot be performed because the
asynchronous motor cannot be disconnected from the load.
Before performing static auto-tuning, properly set the motor type and motor nameplate
parameters of P1-00 to P1-05 first. The AC drive will obtain parameters of P1-06 to P1-08
by static auto-tuning.
Set this parameter to 1, and press
Then, the AC drive starts static auto-tuning.
•
2: Asynchronous motor complete auto-tuning
To perform this type of auto-tuning, ensure that the motor is disconnected from the load.
During the process of complete auto-tuning, the AC drive performs static auto-tuning first
and then accelerates to 80% of the rated motor frequency within the acceleration time set
in P0-17. The AC drive keeps running for a certain period and then decelerates to stop
within deceleration time set in P0-18.
Before performing complete auto-tuning, properly set the motor type, motor nameplate
parameters of P1-00 to P1-05.
Set this parameter to 2, and press Then, the AC drive starts complete autotuning.
Notes
Motor auto-tuning can be performed only in operation panel mode.
Group P2: Vector Control Parameters
Group P2 is valid for vector control, and invalid for V/F control.
Property
Default
Setting
Range
Parameter
Name
Function
Code
Group P2: Vector Control Parameters
☆
30
0–100
Speed loop proportional gain 1
P2-00
☆
0.50s
0.01–10.00s
Speed loop integral time 1
P2-01
☆
5.00HZ
0.00 to P2-05
Switchover frequency 1
P2-02
☆
20
0–100
Speed loop proportional gain 2
P2-03
☆
1.00s
0.01–10.00s
Speed loop
integral
time 2
P2-04
☆
10.0HZ
P2-02 to maximum output
frequency
Switchover frequency 2
P2-05
Содержание SSI700
Страница 1: ......
Страница 3: ...Safety Information and Precautions...
Страница 7: ...Product Information...
Страница 12: ...Mechanical and Electrical Installation...
Страница 19: ...Operation Display and Application Examples...
Страница 42: ...Function Code Table...
Страница 64: ...Description of Function Codes...
Страница 131: ...EMC...
Страница 137: ...Selection and Dimensions...
Страница 141: ...Maintenance and Troubleshooting...