SSI700 User Manual Description of Function Codes
www.ssinverter.info
Property
Default
Setting
Range
Parameter
Name
Function
Code
Group 9: Fault and Protection
☆
0
0: Invalid
1: Decelerate
2: Decelerate to stop
Action selection at
instantaneous power
failure
P9-59
☆
90.0%
80.0%–100.0%
Action pause judging
voltage at instantaneous
power failure
P9-60
☆
0.50s
0.00–100.00s
Voltage rally judging
time at instantaneous
power failure
P9-61
☆
80.0%
60.0%–100.0% (standard bus
voltage)
Action judging voltage
at instantaneous power
failure
P9-62
Upon instantaneous power failure or sudden voltage dip, the DC bus voltage of the AC
drive reduces. This function enables the AC drive to compensate the DC bus voltage
reduction with the load feedback energy by reducing the output frequency so as to keep
the AC drive running continuously.
•
If P9-59 = 1, upon instantaneous power failure or sudden voltage dip, the AC
drive decelerates. Once the bus voltage resumes to normal, the AC drive accelerates to
the set frequency. If the bus voltage remains normal for the time exceeding the value set
in F9-61, it is considered that the bus voltage resumes to normal.
•
If P9-59 = 2, upon instantaneous power failure or sudden voltage dip, the AC
drive decelerates to stop.
Figure 6-26 AC drive action diagram upon instantaneous power failure
Содержание SSI700
Страница 1: ......
Страница 3: ...Safety Information and Precautions...
Страница 7: ...Product Information...
Страница 12: ...Mechanical and Electrical Installation...
Страница 19: ...Operation Display and Application Examples...
Страница 42: ...Function Code Table...
Страница 64: ...Description of Function Codes...
Страница 131: ...EMC...
Страница 137: ...Selection and Dimensions...
Страница 141: ...Maintenance and Troubleshooting...