SSI700 User Manual Function Code
www.ssinverter.info
Property
Default
Setting
Range
Parameter
Name
Function
Code
Group P0: Standard Function Parameters
☆
0
0: Not retentive
1: Retentive
Retentive of digital
setting frequency upon
power failure
P0-23
★
0
0: Maximum frequency (P0-10)
1: Set frequency
2: 100 Hz
Acceleration/D
eceleration
time base frequency
P0-24
Property
Default
Setting
Range
Parameter
Name
Function
Code
Group P1: Motor 1 Parameters
★
0
0: Common asynchronous motor
1: Variable frequency motor
Motor type selection
P1-00
★
Model
Dependent
0.1–4.0 kW
Rated motor power
P1-01
★
Model
Dependent
1–500 V
Rated motor voltage
P1-02
★
Model
Dependent
0.01–655.35 A (AC drive power
≤
55 kW)
Rated motor current
P1-03
★
Model
Dependent
0.01 Hz to maximum frequency
Rated motor frequency
P1-04
★
Model
Dependent
1–65535 RPM
Rated motor rotational
speed
P1-05
★
Model
dependent
0.001–65.535
Ω
(AC drive power
≤
55 kW)
Stator resistance
(asynchronous motor)
P1-06
★
Model
Dependent
0.001–65.535
Ω
(AC drive power
≤
55 kW)
Rotor resistance
(asynchronous motor)
P1-07
★
Model
Dependent
0.01–655.35 mH (AC drive
power
≤
55 kW)
Leakage inductive
reactance (motor)
P1-08
★
Model
Dependent
0.1–6553.5 mH (AC drive power
≤
55 kW)
Mutual inductive
reactance ( motor)
P1-09
★
Model
Dependent
0.01 to P1-03 (AC drive power
≤
55 kW)
No-load current
(asynchronous motor)
P1-10
★
0
0: No auto-tuning
1: Asynchronous motor static
auto-tuning
2: Asynchronous motor complete
auto-tuning
Auto-tuning selection
P1-11
Property
Default
Setting
Range
Parameter
Name
Function
Code
Group P2: Vector Control Parameters
☆
30
0–100
Speed loop proportional
gain 1
P2-00
☆
0.50s
0.01–10.00s
Speed loop integral time 1
P2-01
☆
5.00HZ
0.00 to P2-05
Switchover frequency 1
P2-02
☆
20
0–100
Speed loop proportional
gain 2
P2-03
☆
1.00s
0.01–10.00s
Speed loop
integral
time 2
P2-04
☆
10.0HZ
P2-02 to maximum output
frequency
Switchover frequency 2
P2-05
☆
0.000s
0.000–0.100s
Time constant of speed
loop filter
P2-06
☆
150%
50%–200%
Vector control slip gain
P2-07
☆
64
0–200
Vector control
overexcitation gain
P2-08
☆
150%
0.0%–200.0%
Digital setting of torque
upper limit in speed
control mode
P2-09
Содержание SSI700
Страница 1: ......
Страница 3: ...Safety Information and Precautions...
Страница 7: ...Product Information...
Страница 12: ...Mechanical and Electrical Installation...
Страница 19: ...Operation Display and Application Examples...
Страница 42: ...Function Code Table...
Страница 64: ...Description of Function Codes...
Страница 131: ...EMC...
Страница 137: ...Selection and Dimensions...
Страница 141: ...Maintenance and Troubleshooting...