-80-
No. JXC
※
-OMT0002-C
(7) Area output
-Procedures-
(a) Output the Step data No. (INx).
(b) Turn the "DRIVE" ON. Step data No. 1 (OUTx) will be input.
(c) The BUSY will turn ON and INP will turn OFF (the positioning operation will starts).
(d) The AREA of step data No.1 turns ON (at 150mm from the origin point).
(e) The BUSY will turn OFF and INP will turn ON. (Positioning operation of step data No.1 is
completed).
(f) Output the step data No. 2 (INx).
(g) Turn the "DRIVE" ON. Step data No. 2 (OUTx) will be input.
(h) The AREA will turn OFF. The BUSY will turn ON and INP will turn OFF. (The positioning operation
will start).
(i) The AREA for step data No.2 will turn ON (at 170mm from the origin point).
(j) The AREA for step data No.2 will turn OFF (at 130mm from the origin point).
(k) The BUSY will turn OFF and INP will turn ON. (Positioning operation of step data No.2 is
completed).
- Timing chart -
Initial position: 50mm
↓
Step data No.1 operation (Position: 200mm, Area 1: 150mm, Area 2: 250mm)
↓
Step data No.2 operation (Position: 100mm, Area 1: 130mm, Area 2: 170mm)
Speed
Input
Output
Step Data No.1
Step Data No.2
Operation of step data No.1
Previous step data No.
Input
Output
Speed
The INP signal is OFF when the EMG input is OFF.
The EMG turns ON (Stop release), and the INP signal turns ON when
the actuators are /-"Positioning range" of the target position.
Previous step data No.