-88-
No. JXC
※
-OMT0002-C
(2) Driver alarm
Name of the
controller
setting
software
(code)
G
roup
How to
deactivate
Alarms and countermeasures
Step data
value is wrong
(1-048)
B
RESET
is ON
< Details >
The step data or parameter is incorrect for the following parameter
assignable range.
[Settable range]
(1) Pushing force ≥ Trigger level
(2) Pushing force > 0
(3) Speed ≥ Pushing speed ≥ Minimum speed of the actuator
(4) Pushing speed
Maximum pushing speed of the actuator
(5) Pushing
force ≥ Minimum pushing force of actuator
(6) The Basic parameter "Max pushing force"
minimum pushing
force of the actuator
(7) The Basic parameter "Max pushing force"
“Trigger level”.
<Countermeasure>
Modify the step data and basic parameter settings
Caution
Please refer to the actuator manual or the catalogue for the max/min
pushing force/speed for the actuator.
Parameter
value is wrong
(1-049)
B
RESET
is ON
< Details >
The parameter is incorrect for the following parameter assignable range.
[Settable range]
(1) Stroke (-) < Stroke (+)
(2) Parameter “Max pushing force” < maximum pushing force of the
actuator
<Countermeasure>
Modify the basic parameter settings.
Caution
Please refer to the actuator manual or the catalogue for the max
pushing force for the actuator.
Set stroke is
outside stroke
limit. (1-052)
B
RESET
is ON
< Details >
An alarm is generated when an operation exceeds the basic parameter
"Stroke (+)", "Stroke (-)". (Including JOG operation after a Return to origin)
<Countermeasure>
Make sure that the basic parameters “Stroke (+)” and “Stroke (-)” are
consistent with the distance of the actuator movement specified in the
step data.
Caution
If the step data operation method is a “relative movement”, note the
location where the operation starts and the distance moved.
If the location is outside the stroke range when power is supplied,
this alarm will be generated. Move the table to within the stroke
range, and supply power.