Sunny Island 4500
Installation & Operating Instructions
BWRI45-13-EE0304
- 207 -
SMA Regelsysteme GmbH
„PARALL“ (3+9)
Parameter Unit
Min.
Max.
Default
Description
713_K1 Off t1
(D)
0
10
7
When this battery state is reached, K1 is switched
off.
0: L4
deep-cycle discharge
1: L3
2: L2
3: L1
4: N4
5: N3
6: N2
7: N1
Battery full
8: O1
Overcharge
9: O2
10: O3
714_K1 On t2
(D)
0
10
3
Switch-on threshold for K1 in special period t2 (see
712)
715_K1 Off t2
(D)
0
10
7
Switch-off threshold for K1 in special period t2 (see
713)
716_K2 t2 begin
(C)
h
0
23
0
Beginning of special period t2 for K2 (see 710)
717_K2 t2 end
(C)
h
0
23
0
End of special period t2 for K2 (see 711)
718_K2 On t1
(D)
0
10
5
Switch-on threshold for K2 (see 712)
719_K2 Off t1
(D)
0
10
5
Switch-off threshold for K2 (see 713)
720_K2 On t2
(D)
0
10
5
Switch-on threshold for K2 in special period t2
(see 714)
721_K2 Off t2
(D)
0
10
5
Switch-off threshold for K2 in special period t2
(see 715)
722_K3 t2 begin
(C)
h
0
23
0
Beginning of special period t2 for K3 (see 710)
723_K3 t2 end
(C)
h
0
23
0
End of special period t2 for K3 (see 711)
724_K3 On t1
(D)
0
10
5
Switch-on threshold for K3 (see 712)