Sunny Island 4500
Installation & Operating Instructions
BWRI45-13-EE0304
- 192 -
SMA Regelsysteme GmbH
„PARALL“ (3+9)
Parameter Unit
Min.
Max.
Default
Description
308_Start-Stop
(A)
0
2
1
Can also be set in Menu “START” (2-1), thus, it
cannot be found in the PARSYS-Menu
0: Reserved
1: Start:
Starts the Sunny Island
2: Stop:
Stops the Sunny Island
310_Auto Start
(A)
0
255
0
Number of autostart attempts (0: autostart off)
within one hour. After one hour the counter will be
reset.
Autostart means that approx. 10 sec after a switch-
off (due to error or the like) the Sunny Island re-
starts.
In addition, the Sunny Island starts automatically
after switching on the DC voltage when the
Autostart is activated.
ATTENTION!
The Sunny Island will execute this number of
autostart attempts anew in intervals of one hour.
The Sunny Island’s low battery load mode will be
deactivated if this parameter is set to 0!(s. Parame-
ter “535_State Stop T” for details)
312_COM1 Proto
(D)
0
2
1
Communication protocol COM1:
0: None:
interface not in use
1: SMANET:
interface based on SMANet
protocol
2: SUNNYNET: interface based on SunnyNet
protocol
For communication to Sunny Boys: set to
SUNNYNET
313_COM1 Baud
(D)
0
9
6
Baud rate COM1 (bits/s)
2: 1200
5: 9600
6: 19200
For communication to Sunny Boys or Sunny Boy
Controls: set to 1200
In three-phase operation all inverters have to be
set to 19200!
316_COM2 Proto
(D)
0
2
2
Communication protocol COM2:
0: None:
interface not in use
1: SMANET:
interface based on SMANet pro-
tocol
2: SUNNYNET: interface based on SunnyNet
protocol
For communication to Sunny Boys: set to
SUNNYNET