Sunny Island 4500
Installation & Operating Instructions
BWRI45-13-EE0304
- 193 -
SMA Regelsysteme GmbH
„PARALL“ (3+9)
Parameter Unit
Min.
Max.
Default
Description
317_COM2 Baud
(D)
0
9
2
Baud rate COM2 (bits/s)
2: 1200
5: 9600
6: 19200
For communication to Sunny Boys or Sunny Boy
Controls: set to 1200.
401_Phase Mode
(D)
0
17
0
0: 1Phs_Single:
single-phase operation, inverter
is the only device
1: 1Phs_Psingle: single-phase parallel operation
with one battery per device
(grid and generator not possi-
ble!)
2: 1Phs_Mstr2:
single-phase parallel operation
with two devices with one sin-
gle battery pack, device is mas-
ter
3: 1Phs_Mstr3:
single-phase parallel operation
with three devices with one sin-
gle battery pack, device is mas-
ter
4: 1Phs_Slv2:
single-phase parallel operation
with two or three devices with
one single battery pack, device
is slave 2
5: 1Phs_Slv3:
single-phase parallel operation
with three devices with one sin-
gle battery pack, device is slave
3
6: 3Phs_Mstr1Set: three-phase operation, device
is master (L1)
7; 3Phs_parallel: three-phase operation in droop-
mode (see Chapter 11.7.2 and
11.7.3), device is master (L1)
10: 3Phs_Slv1L2: three-phase operation, device
is slave (L2)
11: 3Phs_Slv1L3: three-phase operation, device
is slave (L3)
402_Uconv nom
(A)
V
200
260
230
Setpoint value of AC voltage which the Sunny Is-
land is to provide in its function as the grid-forming
element (RUN_U)
403_Fconv nom
(A)
Hz
40
70
50 (60)
Setpoint value of AC frequency which the Sunny
Island is to provide in its function as the grid-
forming element (RUN_U)
404_Uext nom
(A)
V
150
260
230
Nominal AC voltage (RUN_I)