Sunny Island 4500
Installation & Operating Instructions
BWRI45-13-EE0304
- 164 -
SMA Regelsysteme GmbH
Parameter settings, recommended for this configuration
The proper settings of the following parameters should be checked. In general, the
system should function well with the default values, but minor optimizations might be
advisable.
Parameter Unit
Default
Description
Master
Slaves
310_Auto Start
0
Number of autostart attempts
3 (?)
X
506_acid density
kg/l
1,24
Nom. acid density acc. to manufac-
turer
1,24 (?)
X
509_Tbat max
°C
40
Max. battery temperature permissi-
ble
40 (?)
X
631_PldzMin
%
60
Charging state below which CHP
will always be started
? X
632_PldzMax
%
85
Charging state above which CHP
will ever be started
? X
633_PConsMin
W
1000
Lower limit for load power
?
X
634_PConsMax
W
3000
Upper limit for load power
?
X
635_PChargeMax
W
3000
Setpoint for charging power
?
X
644_PldOnLx
W
0
Load-dependent activation of CHP
?
X
X: don’t care; ?: system-dependent; <value>(?): preferred setting, but system-dependent at last
Many more parameters will have an effect on the system. But unless there are co-
gent reasons to change them, their default values should be retained unchanged.
For a more detailed description of the parameters refer to Chapter 16.