Sunny Island 4500
Installation & Operating Instructions
BWRI45-13-EE0304
- 98 -
SMA Regelsysteme GmbH
6.3 Configuration after Restart (“Restart”)
If the Sunny Island has already been fully adjusted to an island grid it does not need
to be reconfigured after a restart. All settings are maintained even if the inverter is
switched off. If you still want to change parameters to optimize the system please
follow the instructions below:
When you reach the “INIT“ (0-0) menu after switching on the DC fuse of the Sunny
Island – as described in Chapter 5 – confirm the automatic selection of “Restart“ by
pressing
[ ENTER ]
. This will not change any of the settings already made.
You will thus reach the menu branch selection “SETUP“ (0-3) where – as described
in Chapter 8 – you can change the desired parameters in the corresponding
“PARxxx“ (3+3 ... 3+9) menus after entering the installer password in the “PASSWD”
(3-2) menu.
If you have not pressed
[ ENTER ]
early enough you will reach the menu branch se-
lection “DATA“ (0-1). From here it is also possible to reach all menus with the installer
password and change the parameters there.
Changes of parameters should always be made in standby mode.
Otherwise, the corresponding operating values will change immedi-
ately after pressing [ ENTER ]. Incorrect entries can then not be
changed fast enough and may lead to damages in the plant!
To be sure that the modified parameters will take effect, please follow the
steps below:
1. Set any parameter that has to be changed.
2. Select „Store Permanent“ in the „FUNCT“ (2+3) menu (alternatively
wait for at least 30 seconds without pressing any buttons).
3. Restart the Sunny Island by selecting “Restart” in the “FUNCT” (2+3)
menu (confirm the appearing question with <YES> by pressing
[ ENTER ]
).