Sunny Island 4500
Installation & Operating Instructions
BWRI45-13-EE0304
- 204 -
SMA Regelsysteme GmbH
„PARALL“ (3+9)
Parameter Unit
Min.
Max.
Default
Description
647_ClustMode
(D)
Off
0
3
0: Off:
No special funcion is assigned
to this Sunny Island
1: SupMstr:
Sunny Island is the “Super
Master” that is in charge of con-
trolling the other clusters in the
system and the generator,
where applicable.
2: ClstMstr:
Sunny Island is the Master of a
secondary cluster in the system
that is contolled by a “Super
Master”
3: Reptr:
Sunny Island is the Slave to
which COM2 port another clus-
ter is connected
701_Man K1
(A)
0
2
0
Operating mode of relay K1
0: OFF:
Switch relay K1 off
1: ON:
Switch relay K1 on
2: AUTO:
Sunny Island automatically
controls relay K1.
702_Man K2
(A)
0
2
0
Operating mode of relay K2
0: OFF:
Switch relay K2 off
1: ON:
Switch relay K2 on
2: AUTO:
Sunny Island automatically
controls relay K2.
703_Man K3
(A)
0
2
0
Operating mode of relay K3
0: OFF:
Switch relay K3 off
1: ON:
Switch relay K3 on
2: AUTO:
Sunny Island automatically con-
trols relay K3.
704_Man K4
(A)
0
2
0
Operating mode of relay K4
0: OFF:
Switch relay K4 off
1: ON:
Switch relay K4 on
2: AUTO:
Sunny Island automatically con-
trols relay K4.