User Manual of A90 Series Inverter
173
The slip is 100% during the quick start with large inertia and 0 when the frequency
reaches the set value. Quick increase or decrease of the output frequency will cause
overvoltage or overcurrent. F05.12 filtering can slow down the rise of voltage and current.
Function
code
Function code name
Parameter
description
Unit
Default
setting
Attribute
F05.13
Oscillation suppression gain
0 - 20000
100
●
F05.14
Oscillation suppression cutoff
frequency
0.00-600.00
Hz
55.00
●
This parameter can be adjusted to suppress motor oscillations during the open loop
control (VVF). When the motor does not oscillate, this parameter should not be adjusted as
little as possible or properly reduced. If the motor oscillates obviously, this parameter can
be increased properly.
Function
code
Function code
name
Parameter description
Unit
Default
setting
Attribute
F05.15
Droop
control
frequency
0.00 - 10.00
Hz
0.00
●
This function is usually applied for load distribution when one load is driven by
multiple motors.
Droop control is to reduce the output frequency of the inverter with the load increasing,
so that the output frequency of the motor drops more in the load driven by multiple motors,
thus reducing the load on this motor and leading to evener distribution of the load on
multiple motors.
This parameter refers to the output frequency drop of the inverter under the rated load.
Function code
Function code name
Parameter description Unit
Default
setting
Attribute
F05.16
Energy saving rate
0.00 - 50.00
%
0.00
●
F05.17
Energy saving action time 1.00 - 60.00
s
5.00
●
The energy saving rate (F05.16) reflects the energy saving capacity. The larger the set
value, the more energy will be saved. If the set value is 0.00, energy saving will be invalid.
When energy-saving operation is valid, energy saving control will be enabled once the
energy saving conditions are met and have been maintained for the energy saving time
(F05.17).
The default settings of the VF control optimization parameters of the synchronous