User Manual of A90 Series Inverter
126
t1
Output
frequency
(Hz)
Fbase
Time
(s)
t2
Output
frequency
(Hz)
Fbase
Time
(s)
(a) Acceleration time 1 (b) Deceleration time 1
Fig. 7-4 Acceleration and Deceleration Time
Note that the acceleration and deceleration time is in 0.01 s, 0.1 s or 1s, depending
on the F15.13.
Function code
Function code
name
Parameter description
Unit
Default
setting
Attribute
F00.16
Maximum
frequency
1.00~600.00
Hz
50.00
○
The allowable maximum frequency of the inverter is represented by Fmax. The Fmax
range is from 20.00 to 600.00Hz.
Function
code
Function code name
Parameter description
Unit
Default
setting
Attribute
F00.17
Options of upper
frequency limit
control
0: set by F00.18
1: AI1
2: AI2
3: retention
4: VP (keyboard potentiometer)
5: retention
6: percent setting of upper limit
frequency communication
7: direct setting of upper limit
frequency communication
0
○
F00.18
Upper frequency
limit
Lower frequency limit F00.19 to
maximum frequency F00.16
Hz
50.00
●
F00.19
Lower frequency
limit
0.00 to upper frequency limit
F00.18
Hz
0.00
●
F00.17=0: set by F00.18
The upper frequency limit is set by F00.18.
F00.17=1:AI1