User Manual of A90 Series Inverter
79
0.0 to system acceleration time/2
(F15.13 = 1)
0 to system acceleration time/2
(F15.13 = 2)
F04.19 Stop mode
0: Slow down to stop
1: free stop
0
○
F04.20
Starting frequency of
DC braking in stop
0.00 to maximum frequency
F00.16
Hz
0.00
○
F04.21
DC braking current in
stop
0.0~100.0 (100.0 = Rated current
of motor)
%
50.0
○
F04.22
DC braking time in
stop
0.00~30.00 0.00: invalid
s
0.00
○
F04.23
Demagnetization time
for DC braking in
stop
0.00~30.00
s
0.50
○
F04.24 Flux braking gain
100-150 (100: no flux braking)
100
○
F04.25 Reserved
F04.26
Start mode after
failure/free stop
0: start according to F04.00
setting mode
1: start of speed tracking
0
○
F04.27
Second confirmation
of terminal start
command
0: Not required for confirmation
1: to be confirmed
0
○
F04.28 Reserved
F04.29
Zero
speed
check
frequency
0.00~5.00
Hz
0.25
●
F04.30
Initial position search
after power-on or
fault
0: Invalid
1: valid
1
●
F05
V/F control parameter group
F05.00 V/F curve setting
0: straight line V/F
1: multi-point broken line V/F
2: 1.3-power V/F
3: 1.7-power V/F
4: square V/F
5: VF complete separation mode
(Ud = 0, Uq = K * t = voltage of
separation voltage source)
6: VF semi-separation mode (Ud
= 0, Uq = K * t = F/Fe * 2 *
voltage of separation voltage
source)
0
○