User Manual of A90 Series Inverter
116
F00.03=0: the terminal RUN is in the running status, and F/R in the
forward/reverse status.
Enable/Disable the terminal RUN to control the start and stop of the inverter, and the
terminal F/R to control the forward/reverse running. If F00.21 is set to 1 and reverse
running is disabled, the F/R terminal will not be available. If the mode of deceleration to
stop is selected, the logic diagram is as shown in Fig. 7-1(b).
F00.03=1: the terminal RUN controls forward running, and the terminal F/R is in
the reverse mode.
Enable/Disable the terminal RUN to control the forward running and stop of the
inverter, and the terminal F/R to control the reverse running and stop. When the terminals
RUN and F/R are enabled simultaneously, the inverter will be stopped. If reverse running is
disabled, the terminal F/R will not be available. If the mode of deceleration to stop is
selected, the forward/reverse logic will be run, as shown in Fig. 7-1(d).
Operation
Forward/
reverse
RUN
F/R
COM
24V
Inverter
RUN
F/R
f
Output
frequency
-f
Time
(a) Wiring diagram of two-line control
(F00.03=0)
(b)
Forward/reverse
running
logic
(F04.19=0, F00.03=0)
Reverse
RUN
F/R
COM
24V
Inverter
Forward
RUN
F/R
f
Output
frequency
-f
Time