User Manual of A90 Series Inverter
299
8 CRC check Hi
4
C
Register
value
Hi
(F19.02)
00
9
Register
value
Lo
(F19.02)
00
10
Register
value
Hi
(F19.03)
01
11
Register
value
Lo
(F19.03)
2C
12
Register
value
Hi
(F19.04)
00
13
Register
value
Lo
(F19.04)
00
14
Register
value
Hi
(F19.05)
00
15
Register
value
Lo
(F19.05)
00
16
CRC check Lo
53
17
CRC check Hi
5B
* Tail
≥3.5 characters (idle)
2)
Check whether the line is connected.
Send: 01 08 00 00 AA 55 5E 94
Return:
01 08 00 00 AA 55 5E 94 (normal)
Return:
01 88 04 47 C3 (exception, assuming a slave fault)
Send the invoice to
Normal Return
Exception Return
* Frame header
≥3.5 characters (idle)
1 Address
01 Address
01 Address
01
2 Function
08 Function
08 Function code
88
3 Sub-function
code Hi
00 Sub-function code
Hi
00 Exception code
04 (assumption)
4 Sub-function
code Lo
00 Sub-function code
Lo
00 CRC check Lo
47
5 Data Hi
AA Data Hi
AA CRC check Hi
C3
6 Data Lo
55 Data Lo
55
7 CRC check Lo
5E CRC check Lo
5E
8 CRC check Hi
94 CRC check Hi
94
* Tail
≥3.5 characters (idle)
3)
Change the carrier frequency (F00.23) to 4.0kHz.
(use the function code 0x06 as such
function codes are expected to be stored in EEPROM after change)
Send:
01 06 00 17 00 28 39 D0