F06.21=2: automatic adjustment
In the automatic adjustment, the optimal flux weakening current will be selected
automatically, but it may affect the dynamic performance of the system or become unstable.
The speed of flux weakening current adjustment can be changed by setting the
proportional gain (F06.24) and integral time (F06.25). However, fast adjustment of the flux
weakening current adjustment may cause instability. This does not need to be changed
manually under normal circumstances.
Function
code
Function code name
Parameter description
Unit
Default
setting
Attribute
F06.27
Self-learning gain at
initial position
0 - 200
%
100
●
This parameter is used to determine the amplitude of the high-frequency current
injected during the initial position identification. The larger this value, the higher the
“squeak” sound will be.
Function
code
Function code
name
Parameter description
Unit
Default
setting
Attribute
F06.28
Frequency of low
frequency band of
injection current
0.00-100.00 (100.00 is the
rated frequency of the motor)
%
10.00
●
F06.29
Injection current of
low frequency
band
0.0-60.0 (100.0 is the rated
current of the motor)
%
40.0
●
F06.30
Regulator gain of
low frequency
band of injection
current
0.00 - 10.00
0.50
●
F06.31
Regulator integral
time of low
frequency band of
injection current
0.00 - 300.00
ms
10.00
●
F06.32
Frequency of high
frequency band of
injection current
0.00-100.00 (100.00 is the
rated frequency of the motor)
%
20.00
●
F06.33
Injection current of
high frequency
band
0.0-30.0 (100.0 is the rated
current of the motor)
%
8.0
●
F06.34
Regulator gain of 0.00 - 10.00
0.50
●