User Manual of A90 Series Inverter
146
Function
code
Function code name
Parameter description Unit
Default
setting
Attribute
F02.18
X1 valid delay time
0.000-30.000
s
0.000
●
F02.19
X1 invalid delay time
0.000-30.000
s
0.000
●
F02.20
X2 valid delay time
0.000-30.000
s
0.000
●
F02.21
X2 invalid delay time
0.000-30.000
s
0.000
●
F02.22
X3 valid delay time
0.000-30.000
s
0.000
●
F02.23
X3 invalid delay time
0.000-30.000
s
0.000
●
F02.24
X4 valid delay time
0.000-30.000
s
0.000
●
F02.25
X4 invalid delay time
0.000-30.000
s
0.000
●
Valid delay
Xi input
Delay
processing
Invalid delay
Fig. 7-9 Schematic Diagram of Terminal Delay Sampling
In the event of changes in the status of the function terminal, a response will be made
with delay according to the function code settings. Currently only the terminals X1 to X4
support this function. Specifically, it is embodied in: This function will take effect when the
function terminal changes from the invalid to valid status and is maintained with the valid
delay, and not take effect when the function terminal changes from the valid to invalid
status and is maintained with the invalid delay.
★
If the function code is set to 0.000s, the corresponding delay will be invalid.
Function
code
Function code
name
Parameter description
Unit
Default
setting
Attribute
F02.31
Options of
analog input
function
Ones place:
AI1
0: analog input
1: digital input (0 below 1V, 1 above
3V, the same as last time under 1-3V)
Tens place:
AI2
0: analog input
1: digital input (the same as above)
0000D
○
The analog input terminals AI1 and AI2 of the A90 series inverter can be used as