User Manual of A90 Series Inverter
249
7-23 List of Running Statuses in
Faults.
F19.05
Working time in
failure
Display the working time in the
last fault.
h
0
×
The function codes related to the previous fault are as follows:
Function
code
Function code
name
Parameter description
Unit
Default
setting
Attribute
F19.06
Previous
fault
category
Display the type of the
previous fault, as detailed in
Table 7-22 List of Fault Types.
0
×
F19.07
Output frequency
in failure
Display the output frequency
in the previous fault.
Hz
0.00
×
F19.08
Output current in
failure
Display the output current in
the previous fault.
A
0.00/0.0
×
F19.09
Bus voltage in
failure
Display the bus voltage in the
previous fault.
V
0
×
F19.10
Running status in
failure
Display the running status in
the previous fault, as detailed
in Table 7-23 List of Running
Statuses in Faults.
0
×
F19.11
Working time in
failure
Display the working time in
the previous fault.
h
0
×
The function codes related to the first two faults are as follows:
Function
code
Function code
name
Parameter description
Unit
Default
setting
Attribute
F19.12
Last two fault
categories
Display the types of the first
two faults, as detailed in Table
7-22 List of Fault Types.
0
×
F19.13
Output frequency
in failure
Display the output frequency in
the first two faults.
Hz
0.00
×
F19.14
Output current in
failure
Display the output current in the
first two faults.
A
0.00 /0.0
×
F19.15
Bus voltage in
failure
Display the bus voltage in the
first two faults.
V
0
×
F19.16
Running status in
failure
Display the running status in the
first two faults, as detailed in
Table 7-23 List of Running
Statuses in Faults.
0
×
F19.17
Working time in
failure
Display the working time in the
first two faults.
h
0
×