User Manual of A90 Series Inverter
131
Function code
Function code
name
Parameter description
Unit
Default
setting
Attribute
F00.28
Options of motor
parameter group
0: parameter group of motor 1
1: parameter group of motor 2
0
○
The A90 series inverter supports time-sharing control of two motors. The motor
parameters and control parameters can be set separately. The corresponding parameters of
the motor 1 are in the F00 group, F01 group and F06 group, and those of the motor 2 are in
the F14 group.
The valid motor can be selected in conjunction with F00.28 and the input function
“Motor 1/Motor 2 switching”, as detailed in Table 7-3.
Table 7-3 Details of Motor Parameter Group Options
F00.28: Motor parameter
group options
30: motor 1/motor 2
switching
Valid motor
Related parameter
group
0: parameter group of
motor 1
Invalid
Motor 1
F00/F01/F06
Valid
Motor 2
F14
1: parameter group of
motor 2
Invalid
Motor 2
Valid
Motor 1
F00/F01/F06
Function code
Function code
name
Parameter description
Unit
Default
setting
Attribute
F00.29
User password 0 - 65535
0
○
F00.29 is used to set a password to enable the password protection and prevent the
function code parameters of the inverter from modification by unauthorized personnel. If
the password is set to 0, the password function will be invalid. When a non-zero user
password is set, all parameters (except this function code) can only be viewed and are not
modifiable.
Function code
Function code
name
Parameter description
Unit
Default
setting
Attribute
F00.30
Inverter type
0: G type
1: P type
0
○
F00.30=0
: set the inverter to G type, suitable for mechanical and constant-torque
loads;
F00.30=1
: set the inverter to P type, suitable for fans or pumps (i.e. square or cubic
torque loads).
★
: When the P type is set, refer to the nameplate for the applicable motor power.
This
must not be applied to constant-torque loads.