User Manual of A90 Series Inverter
76
1
0: level
1: single pulse
F03.06
Positive/negative
logic of digital output
D7
D6
D5
D4
D3
D2
D1
D
0
00000
○
*
*
*
*
*
R1
*
Y1
0: positive logic is valid in the
closed state/invalid in the open
state
1: negative logic is valid in the
closed state/invalid in the open
state
F03.08
Output status control
in jog
D7 D6 D5 D4 D3 D2 D1
D
0
00000
○
*
*
*
RE
V
FD
T2
FD
T1
FA
R
R
U
N
0: valid in jogging
1: invalid in jogging
F03.09 Y1 valid delay time
0.000~30.000
s
0.000
●
F03.10 Y1 invalid delay time 0.000~30.000
s
0.000
●
F03.13 R1 valid delay time
0.000~30.000
s
0.000
●
F03.14 R1 invalid delay time 0.000~30.000
s
0.000
●
F03.17
Single pulse time of
Y1 output
0.001~30.000
s
0.250
●
F03.19
Single pulse time of
R1 output
0.001~30.000
s
0.250
●
F03.21
Options of analog
output M1
0: running frequency (absolute
value)
1: set frequency (absolute value)
2: output torque (absolute value)
3: set torque (absolute value)
4: output current
5: Output voltage
6: bus voltage
7: output power
8: AI1
9: AI2
11: VP
13: Communication setting
14: count value
0
○
F03.22
Options of analog
output M2
2
○