28 |
System Configuration |
GN70/MX610/MX612 Operator and Installation Manual
Option
Description
Bus State
Indicates if network backbone is operating. If no data is detected,
check power and check the terminations
Rx Overflows
Value greater than 0 could indicate the software is very busy and
unable to keep up with incoming messages
Rx Overruns
Rx Errors
CAN interface error counters. Count up when there are errors on
the CAN bus, and down when things are okay. Should normally be
0. The bus power is off when 255 is reached. Check same things as
for Bus state if greater than 0 observed
Tx Errors
Fast packet Errors:
Detected errors since power up. Check the network if this is
continually increasing
Rx Messages
A count since power up of messages received / transmitted
Tx Messages
Bus Load
Real time bus load in percentage of max capacity
SimNet Groups
The SimNet Group function is used to control parameter settings, either globally or in groups
of units. The function is used on larger vessels where several SimNet units are connected via
the network. By assigning several units to the same group, a parameter update on one unit
will have the same effect on the rest of the group members.
The illustration below shows a network of three GN70/MX61x units (two on the bridge and
one in the remote area). The two units on the bridge can be made to belong to one group
(i.e. Group #1) so that when the backlight and damping settings is adjusted in one of the
bridge units, the other GN70/MX61x display settings will also change. The third GN70/MX61x
unit in the remote location which does not belong to group #1 will not be affected.
GS70
ENT
MOB
MENU
PAGE
POS
NAV
HDG
AIS
MX61x CONTROL HEAD
ENT
MOB
MENU
PAGE
POS
NAV
HDG
AIS
MX61x CONTROL HEAD
ENT
MOB
MENU
PAGE
POS
NAV
HDG
AIS
MX61x CONTROL HEAD
MX61xJB J-Box
MAIN BRIDGE
REMOTE STATION
Group #1
Group #2
Damping
Controls how quickly the display updates values from sensors.
Increasing the damping applies more averaging or smoothing of the data update rate on the
display.
Damping settings are applied to SimNet units belonging to particular damping SimNet
Groups.
¼
Note:
If the damping factor for heading is high, the captured heading might differ from the
heading read on the display when using the heading capture function.