Introduction
6
7SS52 V4 Manual
C53000-G1176-C182-3
•
Output of indications to
−
Control center
−
LEDs
−
Binary outputs of the central unit
•
Commissioning support by measuring and display functions, and output of indica-
tions to a control center as well as to LEDs and outputs of the central unit.
Busbar
protection
The digital busbar protection contains the following functions:
•
Evaluation of the differential current in conjunction with through-current stabilization
(Figure 1-2, page 7)
•
Trip decision based on 3 independent measurements. 2 measurements are based
on busbar configuration, and the third measurement considers all busbar sections
independent of the isolator replica (check zone).
•
Fast tripping (typical trip time 15 ms)
•
Busbar protection with up to 12 bus zones (BZ), 12 bus coupler (auxiliary bus) sec-
tions (AB) and up to 48 bay units
•
Protection of systems with up to quintuple busbars (including transfer busbars)
•
Stabilization against spurious tripping in case of external faults and CT saturation
•
Zone-selective and phase-selective blocking of the busbar protection by the differ-
ential current monitor
•
Selective blocking of the bus section in case of
−
Isolator faults
−
Bay faults (bay unit, FO cable)
−
Measured value error
−
Response of the zero crossing supervision
•
Characteristics for check zone and bus-selective zones can be set independently
from each other
−
Normal pick-up characteristic (Figure 1-2, page 7)
−
Earth fault characteristic (Figure 1-3, page 7)
•
Matching to different CT ratios without interposing matching transformers
•
Selective clearance of short-circuits even on the bypass bus with signal transmis-
sion to the remote end
•
Detection and disconnection of short-circuits in the coupler bay between current
transformers and circuit-breaker based on current measurement and selective un-
balance
•
Detection and disconnection of short-circuits between current transformers and cir-
cuit-breaker of a line by end fault protection
www
. ElectricalPartManuals
. com
Содержание SIPROTEC 7SS522 V4.6
Страница 326: ...Maintenance and Repair 310 7SS52 V4 Manual C53000 G1176 C182 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 432: ...Appendix 416 7SS52 V4 Manual C53000 G1176 C182 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 438: ...Index 422 7SS52 V4 Manual C53000 G1176 C182 34 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...