Control During Operation
242
7SS52 V4 Manual
C53000-G1176-C182-3
Enter date and time in the corresponding boxes. Observe the correct notation
(see Figure 6-26, page 242).
Click
OK
to transfer the specified values into the device. The existing values are
modified and the current dialog box closes.
Figure 6-26 Set clock & date in device
dialog box
If you want to change the time offset or the tolerance time of the clock signal in the
event of a fault, click
Settings
(Figure 6-27, page 242). The setting groups are
shown in the function selection.
Figure 6-27 Selecting the time synchronization function
Double-click
Time Synchronization
. The Time Synchronization & Time Format dia-
log box opens (Figure 6-28, page 243).
Change the time delay of the annunciation under the heading Monitoring (
Fault in-
dication after:
) and the time offset in the box
Offset to time signal
.