Parameter Listing - Central Unit
365
7SS52 V4 Manual
C53000-G1176-C182-3
A.7
Parameter Listing - Central Unit
In the running text of the manual, "XX" is usually used as variable for the first digit
(number of the bay unit) of the parameters 106A to 156A (XX12 instead of 112).
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments
106A
Combi-Coupler
BU@
YES
NO
NO
Combi-Coupler
112
Bay status
BU@
out of service
in service
maintenance
in service
Bay status
113
I>TRIP
BU@
0.00 .. 25.00 I/In
0.00 I/In
Current threshold for TRIP release
114
BF BI MODE
BU@
1-ch w/o sup
1-ch w sup
2-ch w/o sup
2-ch w sup
1-ch w sup
Binary input mode / supervision BF
115
BF OP MODE
BU@
non existent
external
BZ unbalance
trip rep/unbal
I>query
trip rep/I>quer
BZ unbalance
Operation mode BF
116
BF I<
BU@
ON
OFF
OFF
Low-current mode BF
117
TRIP REP. MODE
BU@
1pole
3pole
1pole
TRIP repeat mode
118
I> BF
BU@
0.10 .. 2.00 I/In
0.50 I/In
Current threshold for BF
119
I> BF-EF
BU@
0.05 .. 2.00 I/In
0.25 I/In
Current threshold for BF - EF
120
T-BF-1P
BU@
0.05 .. 10.00 sec
0.25 sec
Time delay for BF with 1-pole faults
121
T-BF-mP
BU@
0.05 .. 10.00 sec
0.25 sec
Time delay for BF with multi-pole faults
122
T-BF I<
BU@
0.05 .. 10.00 sec
0.25 sec
Time delay for BF low current mode
123A
T-BF IMP
BU@
0.05 .. 10.00 sec
0.50 sec
Time delay for BF pulse mode
124
T-BF CB fault
BU@
0.00 .. 10.00 sec
0.10 sec
Time delay BF after CB fault
125
T-TRIP repeat
BU@
0.00 .. 10.00 sec
0.12 sec
Time delay for TRIP repeat
126
T-CB open
BU@
0.00 .. 10.00 sec
0.00 sec
Time delay for CB open
127
T-BF rel sup
BU@
0.02 .. 15.00 sec
15.00 sec
Supervision bin. input BF-release
128
T-BF 2chan
BU@
0.06 .. 1.00 sec
0.06 sec
Supervision time BF start / release
129
End Fault Prot
BU@
ON
OFF
OFF
End fault protection
151A
Maint. Iso1
BU@
YES
NO
YES
Maintenance for Isolator 1
152A
Maint. Iso2
BU@
YES
NO
YES
Maintenance for Isolator 2
153A
Maint. Iso3
BU@
YES
NO
YES
Maintenance for Isolator 3
154A
Maint. Iso4
BU@
YES
NO
YES
Maintenance for Isolator 4
155A
Maint. Iso5
BU@
YES
NO
YES
Maintenance for Isolator 5
156A
Maint. CB
BU@
YES
NO
YES
Maintenance for CB
5104
FREQUENCY
P.System Data 1
50 Hz
60 Hz
50 Hz
Nominal frequency
5108A
Test mode SK
Protec. general
OFF
ON
OFF
Test mode for module SK
5111A
Language BU
Protec. general
German
English
French
Spanish
Italian
Russian
English
Language of bay units
5112A
OutEn BU-TEST
Protec. general
NO
YES
NO
Output enable bay unit under test
www
. ElectricalPartManuals
. com
Содержание SIPROTEC 7SS522 V4.6
Страница 326: ...Maintenance and Repair 310 7SS52 V4 Manual C53000 G1176 C182 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 432: ...Appendix 416 7SS52 V4 Manual C53000 G1176 C182 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 438: ...Index 422 7SS52 V4 Manual C53000 G1176 C182 34 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...