Functions
130
7SS52 V4 Manual
C53000-G1176-C182-3
The parameter
XX17/CU
) is used to select the operating mode
for TRIP repetition with 1-pole initiation.
With setting
, a single-pole TRIP repetition will be generated in the case of a
single-pole start. The feeder current of the initiating phase and at least one of the other
currents (phase or ground current) must exceed for this the threshold
I> BF
(
XX18/
CU
) or
I> BF-EF
(
XX19/CU
) (ILx & IE).
With setting
3pole
a 3-pole TRIP repetition will be generated in this case. The feeder
current of the initiating phase and at least one of the other currents (phase or ground
current) must exceed for this the threshold
I> BF-EF
(
XX19/CU
) (ILx & IE).
Precondition for a TRIP repetition is a circuit-breaker, which is ready for operation, i.e.
a non-active binary input ">CB not ready" (
FNo. 7619/BU
)(exception: low-current
mode).
The parameter
XX20/CU
) is used to delay for 1-pole faults the TRIP com-
mand and the transfer trip signal issued by the breaker failure protection.
It is recommended for the single-stage breaker failure protection to set this parameter
to twice the circuit breaker trip time.
With two-stage breaker failure protection two time stages pick up:
(
XX25/CU
) and
XX20/CU
).
The tripping of the affected bus zone takes place after the second stage has been pro-
cessed. The parameter
T-BF-1P
(
XX20/CU
) is then to be set higher than the sum of
the delay times set with parameters
T-TRIP repeat
(
XX25/CU
) and the time the
circuit breaker requires for tripping in order to avoid premature or unnecessary tripping
of the bus zone.
The parameter
XX21/CU
) is used to delay for multipole faults the TRIP
command and the transfer trip signal issued by the breaker failure protection.
It is recommended for the single-stage breaker failure protection to set this parameter
to twice the circuit breaker trip time.
With two-stage breaker failure protection two time stages pick up:
(
XX25/CU
) and
XX21/CU
).
The tripping of the affected bus zone takes place after the second stage has been pro-
cessed. The parameter
T-BF-mP
(
XX21/CU
) is then to be set higher than the sum of
the delay times set with parameters
T-TRIP repeat
(
XX25/CU
) and the time the
circuit breaker requires for tripping in order to avoid premature or unnecessary tripping
of the bus zone.
The parameter
XX22/CU
) is used to delay for the "low-current" mode the
TRIP command and the transfer trip signal issued by the breaker failure protection.
The parameter
T-BF IMP
(
XX23A/CU
) is used to delay for pulse mode the feeder-
selective TRIP repetition issued by the breaker failure protection.
The parameter
T-BF CB fault
(
XX24/CU
) is used to delay the TRIP command and
the transfer trip signal. These are issued by the breaker failure protection if a circuit
breaker malfunction is detected in this feeder.
www
. ElectricalPartManuals
. com
Содержание SIPROTEC 7SS522 V4.6
Страница 326: ...Maintenance and Repair 310 7SS52 V4 Manual C53000 G1176 C182 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 432: ...Appendix 416 7SS52 V4 Manual C53000 G1176 C182 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 438: ...Index 422 7SS52 V4 Manual C53000 G1176 C182 34 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...