List of Information - Bay Unit
387
7SS52 V4 Manual
C53000-G1176-C182-3
7612
>CBF L2
>Circuit breaker failure start phase L2
on
IOT
1
TA
194
71
7613
>CBF L3
>Circuit breaker failure start phase L3
on
IOT
1
TA
194
72
7614
>CBF puls
>Circuit breaker failure pulse
on
IOT
1
TA
194
73
7615
>CBF release
>Circuit breaker failure release
on/off
IOT
1
TA
194
74
7616
>TRIP release
>Trip release
on/off
IOT
1
TA
194
75
7617
>CB OFF
>Circuit breaker open
on/off
IOT
7618
>CB man.close
>Circuit breaker manual close
on
IOT
1
TA
194
77
7619
>CB not ready
>Circuit breaker not ready
on/off
IOT
1
GI
194
78
7620
>Bay o.of ser.
>Bay out of service
on/off
IOT
1
GI
194
79
7621
>CBF 3-pole
>Circuit breaker failure start 3-pole
on/off
IOT
1
TA
194
80
7622
>CBF rel.3p.
>Circuit breaker failure release 3-pole
on/off
IOT
1
TA
194
81
7623
>CB ON
>Circuit breaker closed
on/off
IOT
7624
>Isol.maint. >Isolator
maintenance
on/off
IOT
1
GI
194
83
7625
>b.u.CBF L1
>Back-up breaker failure start phase L1
on
IOT
1
TA
194
84
7626
>b.u.CBF L2
>Back-up breaker failure start phase L2
on
IOT
1
TA
194
85
7627
>b.u.CBF L3
>Back-up breaker failure start phase L3
on
IOT
1
TA
194
86
7628
>b.u.CBF 3pol
>Back-up breaker failure start 3-pole
on
IOT
1
TA
194
87
7629
>Blk.BB TRIP
>Block TRIP commands of whole busbar
on
IOT
7630
BB flt.detect
Busbar protection: Fault detected
on
2
GI
194
90
7631
BB Trip L123
Busbar protection: Trip in phase L123
on
OT
2
TA
194
100
7632
CBF Trp.rp.3p
CBF protection: Trip repeat phase L123
on
OT
2
TA
194
101
7633
CBF Trp.rp.L1
CBF protection: Trip repeat phase L1
on
OT
2
TA
194
102
7634
CBF Trp.rp.L2
CBF protection: Trip repeat phase L2
on
OT
2
TA
194
103
7635
CBF Trp.rp.L3
CBF protection: Trip repeat phase L3
on
OT
2
TA
194
104
7636
CB Test L1
Circuit breaker test: Trip phase L1
on
OT
2
194
105
7637
CB Test L2
Circuit breaker test: Trip phase L2
on
OT
2
194
106
7638
CB Test L3
Circuit breaker test: Trip phase L3
on
OT
2
194
107
7639
BB intertrip
Busbar protection: Intertrip
on
OT
2
194
108
7640
Bay o.of serv.
Bay is out of service
on/off
OT
7641
Isol.mainten.
Isolator maintenance
on/off
OT
7642
CB not plaus.
State of circuit breaker not plausible
on/off
OT
1
194
124
7643
CBF Trip L123
CBF protection: Trip L123
on
OT
2
TA
194
125
7644
End-Flt. Trip
End fault protection: Trip phase L123
on
OT
2
TA
194
126
7645
Trip blocked
Trip is blocked by Central Unit
on/off
OT
7646
CBF-Prot.bloc
CBF protection blocked by Central Unit
on/off
OT
7650
Fail Com.CU
Failure in communication w.Central Unit
on/off
O
1
GI
194
121
7651
Param.f.CU Receiving
parameters from Central Unit
on
1
194
122
7652
Fail MV.Offs.
Failure in offset of measured values
on/off
O
1
GI
194
129
7656
CT inversion
Inversion polarity of curr. transformer
on/off
OT
7657
BB TRIP block
TRIP commands of whole busbar blocked
on/off
OT
7658
BF BZ blkd.
BF (ext.start) of whole busbar blocked
on/off
OT
7659
Test mode
Test mode of protective functions
on/off
OT
FNo.
Short Text
Logical Function
Log Buffers
Configurable
in Matrix
IEC 60870-5-103
Eve
n
t Log On/
O
ff
Meas
u
red Val
u
e
Tr
ip
(Faul
t)
Log On/
O
ff
Bi
nar
y
Inp
u
t I
Bi
na
ry
O
utput O
(L
E
D
, al
ar
m re
la
y
)
Tr
ip R
e
la
y
T
Data
Unit
Com
p
atibl
e
Annunci
a
ti
on
G
e
n
e
ra
l I
n
te
rr
ogation
Ann
unc. for
Faul
t
Rec
. Buffer
(Tagged)
Type (p: C
o
rrespond
s
t
o
param
e
ter “Function
type“)
In
fo
rma
tio
n
Num
b
e
r
www
. ElectricalPartManuals
. com
Содержание SIPROTEC 7SS522 V4.6
Страница 326: ...Maintenance and Repair 310 7SS52 V4 Manual C53000 G1176 C182 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 432: ...Appendix 416 7SS52 V4 Manual C53000 G1176 C182 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 438: ...Index 422 7SS52 V4 Manual C53000 G1176 C182 34 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...