Parameter Listing - Bay Unit
367
7SS52 V4 Manual
C53000-G1176-C182-3
A.8
Parameter Listing - Bay Unit
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments
1101
CT STARPNT
Power System
Data
TOWARDS LINE
TOWARDS BUSBAR
TOWARDS LINE
Current transformer polarity
1105
In PRIMARY
Power System
Data
10..20000 A
400 A
Primary Rated current
1141
T TRIP
Power System
Data
0.01..32.00 s
0.15 s
Minimum trip command duration
1201
O/C PHASES
O/C Protection
Phases
ON
OFF
ON
O/C protection for phase faults
1202
I>>
O/C Protection
Phases
0.05..25.00 I/I
N
2.00 I/I
N
Pick-up value of the high-set stage
I>>
1203
T-I>>
O/C Protection
Phases
0.00..60.00 s
0.10 s
Trip time delay of the high-set stage
1206
MEAS.REPET
O/C Protection
Phases
NO
YES
NO
Measurement repetition
1211
CHARACTER.
O/C Protection
Phases
NORMAL INVERSE
VERY INVERSE
EXTREMELY INVERS.
NORMAL INVERSE
Characteristic of the O/C stage Ip
1212
I>
O/C Protection
Phases
0.05.. 25.00 I/I
N
1.00 I/I
N
Pick-up value of the overcurrent
stage I>
1213
T-I>
O/C Protection
Phases
0.00..60.00 s
infinite
0.50 s
Trip time delay of the overcurrent
stage I>
1214
Ip
O/C Protection
Phases
0.10..4.00 I/I
N
1.00 I/I
N
Pick-up value inverse time O/C
stage Ip
1215
T-Ip
O/C Protection
Phases
0.05..10.00 s
0
infinite
0.50 s
Trip time delay inverse time O/C
stage Ip
1216
RMS FORMAT
O/C Protection
Phases
FUNDAMENTAL
TRUE RMS
FUNDAMENTAL
RMS format for inverse time O/C
protection
1221
MAN.CLOSE
O/C Protection
Phases
I>> UNDELAYED
I>/Ip UNDELAYED
INEFFECTIVE
I>> UNDELAYED
Overcurrent stage valid for phase
currents when the circuit breaker is
manually closed
1501
O/C EARTH
O/C Protection
Earth
ON
OFF
ON
O/C protection for earth faults
1502
IE>>
O/C Protection
Earth
0.05..25.00 I/I
N
0.50 I/I
N
Pick-up value of the high-set stage
IE>>
1503
T-IE>>
O/C Protection
Earth
0.00..60.00 s
0.50 s
Trip time delay of the high-set stage
IE>>
1506
MEAS.REPET
O/C Protection
Earth
YES
NO
NO
Measurement repetition
1511
CHARACTER.
O/C Protection
Earth
NORMAL INVERSE
VERY INVERSE
EXTREMELY INVERS
NORMAL INVERS
Characteristic of the O/C stage IEp
1512
IE>
O/C Protection
Earth
0.05..25.00 I/I
N
0.20 I/I
N
Pick-up value of the overcurrent
stage IE>
1513
T-IE>
O/C Protection
Earth
0.00..60.00 s
infinite
0.50 s
Trip time delay of the overcurrent
stage IE>
1514
IEp
O/C Protection
Earth
0.10..4.00 I/I
N
0.10 I/I
N
Pick-up value inverse time O/C
stage IEp
1515
T-IEp
O/C Protection
Earth
0.05..10.00 s
0
infinite
0.50 s
Trip time delay inverse time O/C
stage IEp
www
. ElectricalPartManuals
. com
Содержание SIPROTEC 7SS522 V4.6
Страница 326: ...Maintenance and Repair 310 7SS52 V4 Manual C53000 G1176 C182 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 432: ...Appendix 416 7SS52 V4 Manual C53000 G1176 C182 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 438: ...Index 422 7SS52 V4 Manual C53000 G1176 C182 34 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...