Settings
85
7SS52 V4 Manual
C53000-G1176-C182-3
4.7.2
Date/Clock Management
The integrated date/clock management enables the exact timely assignment of events
e.g., those in the operational annunciations and fault annunciations or in the lists of
the minimum/maximum values. The time can be influenced by
•
the internal clock RTC (Real Time Clock),
•
external synchronisation sources (DCF77, IRIG B, SyncBox, IEC 60870-5-103,
IEC 60850),
•
external minute pulses via binary input.
Time
synchronization
You find the parameters for the clock management in DIGSI at
Settings
→
Time Syn-
chronization
Figure 4-34 The window Settings in DIGSI
−
Example
Double-click
Time Synchronization
. The
Time Synchronization & Time Format
di-
alog box opens (Figure 4-35, page 86).
Note
Upon delivery of the device the internal clock RTC is always set by default as synchro-
nisation source, regardless of whether the device is equipped with a system port or
not. If the time synchronisation is to be accomplished by an external source, you must
select the latter.
www
. ElectricalPartManuals
. com
Содержание SIPROTEC 7SS522 V4.6
Страница 326: ...Maintenance and Repair 310 7SS52 V4 Manual C53000 G1176 C182 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 432: ...Appendix 416 7SS52 V4 Manual C53000 G1176 C182 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 438: ...Index 422 7SS52 V4 Manual C53000 G1176 C182 34 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...