Protection General
175
7SS52 V4 Manual
C53000-G1176-C182-3
5.9.10 List of Information from the Central Unit
$00, .., $03 are variables which will be automatically replaced on entry in the event
buffer by
$00 Number of the bay unit
$01 Bay name
$02 Name of the switching element (e.g. isolator or circuit breaker)
$03 Name of the bus zone
5.9.11 Settings for the Bay Unit
FNo.
Alarm
Comments
10445
Device trip G
Device Trip (group alarm)
10449
Trip BBP G
Trip command BBP (group alarm)
10471
IsoProhib G
Isolator oper. prohibited (group alarm)
10478
>EF charact.
>Earth fault characteristic active
10486
TripRelErr
Timing error trip release
10487
>TRIP-Release
>TRIP-Release for external command
176.1135 $01 $02
$01 circuit breaker $02
177.1341 Trip $03 G
Trip command for $03 (group alarm)
177.1360 >Trip $01
>Trip command for $03
177.1361 TripBIErr $03
Timing error ext. Trip command $03
177.1362 noTripRel $03
No release of Trip command $03
177.1363 Trip BI $03
Trip command by BI for $03
Addr.
Setting Title
Setting Options
Default Setting
Comments
128
T-BF 2chan
0.06 .. 1.00 s
0.06 s
Supervision time BF start / re-
lease
1141
T TRIP
0.01..32.00 s
0.15 s
Minimum trip command duration
7101
LANGUAGE
integrated operator control
DEUTSCH
ENGLISH
FRANCAIS
ESPANOL
ITALIANO
PYCCK.
ENGLISH
www
. ElectricalPartManuals
. com
Содержание SIPROTEC 7SS522 V4.6
Страница 326: ...Maintenance and Repair 310 7SS52 V4 Manual C53000 G1176 C182 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 432: ...Appendix 416 7SS52 V4 Manual C53000 G1176 C182 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 438: ...Index 422 7SS52 V4 Manual C53000 G1176 C182 34 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...