Functions
132
7SS52 V4 Manual
C53000-G1176-C182-3
5.3.7
Settings for the Central Unit
Addr.
Setting Title
Setting Options
Default Setting
Comments
114
BF BI MODE
1-ch w/o sup
1-ch w sup
2-ch w/o sup
2-ch w sup
1-ch w sup
Binary input mode / supervision
BF
115
BF OP MODE
non existent
external
BZ unbalance
trip rep/unbal
I>query
trip rep/I>quer
BZ unbalance
Operation mode BF
116 BF
I<
ON
OFF
OFF Low-current
mode
BF
117
TRIP REP. MODE
1pole
3pole
1pole TRIP
repeat
mode
118
I> BF
0.10 .. 2.00 I / In
0.50 I / In
Current threshold for BF
119
I> BF-EF
0.05 .. 2.00 I / In
0.25 I / In
Current threshold for BF - EF
120
T-BF-1P
0.05 .. 10.00 s
0.25 s
Time delay for BF with 1-pole
faults
121
T-BF-mP
0.05 .. 10.00 s
0.25 s
Time delay for BF with multi-pole
faults
122
T-BF I<
0.05 .. 10.00 s
0.25 s
Time delay for BF low current
mode
123A
T-BF IMP
0.05 .. 10.00 s
0.50 s
Time delay for BF pulse mode
124
T-BF CB fault
0.00 .. 10.00 s
0.10 s
Time delay BF after CB fault
125
T-TRIP repeat
0.00 .. 10.00 s
0.12 s
Time delay for TRIP repeat
127
T-BF rel sup
0.02 .. 15.00 s
15.00 s
Supervision bin. input BF-re-
lease
128
T-BF 2chan
0.06 .. 1.00 s
0.06 s
Supervision time BF start / re-
lease
6106
Tmin TRIP
0.01 .. 32.00 s
0.15 s
Minimum duration of TRIP com-
mand
6320A EF
charact.
released
blocked
blocked
Earth fault characteristic switch-
over
www