Appendix
368
7SS52 V4 Manual
C53000-G1176-C182-3
1516
RMS FORMAT
O/C Protection
Earth
FUNDAMENTAL
TRUE RMS
FUNDAMENTAL
RMS format for inverse time O/C
protection
1521
MAN.CLOSE O/C
Protection
Earth
IE>> UNDELAYED
IE>/IEp UNDELAY.
INEFFECTIVE
IE>> UNDELAYED
Overcurrent stage valid for phase
currents when the circuit breaker is
manually closed
2801
T-Annunc.1
User Logic Func-
tions
0.00..10.00 s
0.00 s
Delay time for 1st user defined an-
nunciation
2802
T-Annunc.2
User Logic Func-
tions
0.00..10.00 s
0.00 s
Delay time for 2nd user defined an-
nunciation
2803
T-Annunc.3
User Logic Func-
tions
0.00..10.00 s
0.00 s
Delay time for 3rd user defined an-
nunciation
2804
T-Annunc.4
User Logic Func-
tions
0.00..10.00 s
0.00 s
Delay time for 4th user defined an-
nunciation
2811
ANNUN1byCU
User Logic Func-
tions
NO
YES
0.00 s
Processing of annunciation 1 by
central unit
2812
ANNUN2byCU
User Logic Func-
tions
NO
YES
0.00 s
Processing of annunciation 2 by
central unit
2813
ANNUN3byCU
User Logic Func-
tions
NO
YES
0.00 s
Processing of annunciation 3 by
central unit
2814
ANNUN4byCU
User Logic Func-
tions
NO
YES
0.00 s
Processing of annunciation 4 by
central unit
2821
ANN1Fct.No
User Logic Func-
tions
0..9999
0
Binary input annunciation (Fct.no)
by annunc.1
2822
ANN2Fct.No
User Logic Func-
tions
0..9999
0
Binary input annunciation (Fct.no)
by annunc.2
2823
ANN3Fct.No
User Logic Func-
tions
0..9999
0
Binary input annunciation (Fct.no)
by annunc.3
2824
ANN4Fct.No
User Logic Func-
tions
0..9999
0
Binary input annunciation (Fct.no)
by annunc.4
2831
ANN1Inp.No
User Logic Func-
tions
0..9999
0
Input-annunciation (Fct.no) for
userdef. logic1
2832
ANN2Inp.No
User Logic Func-
tions
0..9999
0
Input-annunciation (Fct.no) for
userdef. logic2
2833
ANN3Inp.No
User Logic Func-
tions
0..9999
0
Input-annunciation (Fct.no) for
userdef. logic3
2834
ANN4Inp.No
User Logic Func-
tions
0..9999
0
Input-annunciation (Fct.no) for
userdef. logic4
3901
BackUp CBF
Back-Up Breaker
Fail.Protection
OFF
ON
OFF
State of back-up circuit breaker fail-
ure prot.
3911
B.U.CBF-I
Back-Up Breaker
Fail.Protection
0.10..4.00 I/I
N
0.50 I/I
N
Current threshold of back-up break-
er fail.prot
3912
B.U.CBF-T
Back-Up
Break.Fail.Prot.
0.06..60.00 s; +*
0.12 s
Time delay of back-up breaker fail-
ure prot.
4101
CU-INTERF.
Tests
Interface to central unit
4201
BLOCKAGE
Tests
Switch on the blockage of busbar
trip
4202
BLOCKAGE
Tests
Switch off the blockage of busbar
trip
4301
BLOCKAGE
Tests
Switch on the blockage of BF-pro-
tec.ext.start
4302
BLOCKAGE
Tests
Switch off the blockage of BF-pro-
tec.ext.start
4401
CB TRIP
Tests
Circuit breaker trip test 1pole L1
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments
www
. ElectricalPartManuals
. com
Содержание SIPROTEC 7SS522 V4.6
Страница 326: ...Maintenance and Repair 310 7SS52 V4 Manual C53000 G1176 C182 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 432: ...Appendix 416 7SS52 V4 Manual C53000 G1176 C182 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 438: ...Index 422 7SS52 V4 Manual C53000 G1176 C182 34 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...