Circuit breaker failure protection (CBF), selectable per bay, for low-current faults in
the variants
−
I
>
query (1-stage CBF)
−
TRIP repetition with overcurrent detection I
>
(2-stage CBF)
−
Unbalancing (1-stage CBF)
−
TRIP repetition with following unbalancing (2-stage CBF)
−
Single-pole or three-pole start by external breaker failure protection and tripping
via the isolator replica
•
Direct operation of the circuit breaker by the bay unit
•
Direct tripping of busbar sections via binary inputs of the central unit
Figure 1-2 Pick-up characteristics of the busbar and breaker failure protection (unbalancing)
Figure 1-3 Earth fault characteristic