Functions
2.10 Automatic Reclosure Function (optional)
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011
147
For the 4th cycle:
5th to 8th Reclose Cycle
If more than four cycles were set during configuration of the functional scope, the dead times preceding the fifth
(5th) through the ninth (9th) reclosing attempts are equal to the open circuit breaker time which precedes the
fourth (4th) reclosing attempt.
3483 4.AR: START
Start in 4th cycle generally allowed
3484 4.AR: T-ACTION
Action time for the 4th cycle
3486 4.AR Tdead 1Flt
Dead time after 1-phase pickup
3487 4.AR Tdead 2Flt
Dead time after 2-phase pickup
3488 4.AR Tdead 3Flt
Dead time after 3-phase pickup
3489 4.AR Tdead1Trip
Dead time after 1-pole tripping
3490 4.AR Tdead3Trip
Dead time after 3-pole tripping
3491 4.AR: Tdead EV.
Dead time after evolving fault
3492 4.AR: CB? CLOSE
CB ready interrogation before reclosing
3493 4.AR SynRequest
Sync. check after 3-pole tripping
Содержание SIPROTEC 7SD610
Страница 16: ...Contents SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 16 ...
Страница 267: ...Functions 2 18 Command Processing SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 267 ...
Страница 268: ...Functions 2 18 Command Processing SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 268 ...
Страница 428: ...Appendix A 10 Measured Values SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 428 ...
Страница 430: ...Literature SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 430 ...
Страница 442: ...Glossary SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 442 ...
Страница 448: ...Index SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 448 ...